A<br />

Contactors<br />

NEMA/EEMAC Rated Contactors DILM-00N DILM-0N<br />

General<br />

Technical Data<br />

NEMA/EEMAC Rated Contactors<br />

Standards<br />

Lifespan, mechanical<br />

UL, CSA, IEC/EN60947, VDE 0660<br />

AC operated Operations [x 106 ] 10 10<br />

DC operated Operations [x 106 ] 10 10<br />

Max. Operating frequency, mechanical<br />

AC operated [Ops/h] 9000 9000<br />

DC operated<br />

Climatic proofing<br />

[Ops/h] 9000 9000<br />

Open Damp heat constant to IEC60068-2-78<br />

Enclosed<br />

Ambient temperature<br />

Damp heat, cyclic, to IEC60068-2-30<br />

Open [C]<br />

-25 °C…60 °C<br />

-25 °C…60 °C<br />

[F]<br />

-13 °F…140 °F<br />

-13 °F…140 °F<br />

Enclosed [C]<br />

-25 °C…40 °C<br />

-25 °C…40 °C<br />

[F]<br />

-13 °F…104 °F<br />

-13 °F…104 °F<br />

Storage [C]<br />

-40 °C…80 °C<br />

-40 °C…80 °C<br />

Mounting position<br />

AC and DC<br />

Mechanical shock resistance (IEC/EN 60068-2-27)<br />

Half-sinusoidal shock, 10 ms<br />

[F]<br />

-40 °F…176 °F<br />

-40 °F…176 °F<br />

Main Contacts NO contacts Make [g] 10 10<br />

NO/NC contacts Make/Break [g] – –<br />

Auxiliary contacts NO contacts Make [g] 7 7<br />

NC contacts Break [g] 5 5<br />

Degree of protection IP20 IP20<br />

Protection against direct contact when actuated from front (IEC536)<br />

Weight<br />

Finger and-back-of-hand proof<br />

AC [kg] 0.23 0.23<br />

DC<br />

Main terminals<br />

[kg] 0.28 0.28<br />

Wire Capacity minimum [AWG] 18 AWG (single or double) 18 AWG (single or double)<br />

(Cu cable)<br />

Main cable cross sections<br />

maximum [AWG] 14 AWG (single or double) 14 AWG (single or double)<br />

Solid [mm2 ] 1 x (0.75-4.0) 1 x (0.75-4.0)<br />

Flexible <strong>with</strong> ferrule [mm2 ] 1 x (0.75-2.5)<br />

1 x (0.75-2.5)<br />

2 x (0.75-2.5)<br />

2 x (0.75-2.5)<br />

Flexible <strong>with</strong> cable lug [mm2 ] – –<br />

Stranded [mm2 ] – –<br />

Stranded <strong>with</strong> cable lug [mm2 ] – –<br />

Flat conductor Number of segments x width x thickness [mm] – –<br />

Bus bar Width [mm] – –<br />

Main cable connection screw/bolt M3.5 M3.5<br />

Tightening torque<br />

Control circuit cable cross sections<br />

[Nm] 1.2 1.2<br />

Solid [mm2 ] 1 x (0.75-4.0)<br />

1 x (0.75-4.0)<br />

2 x (0.75-2.5)<br />

2 x (0.75-2.5)<br />

Flexible <strong>with</strong> ferrule [mm2 ] 1 x (0.75-2.5)<br />

1 x (0.75-2.5)<br />

2 x (0.75-2.5)<br />

2 x (0.75-2.5)<br />

Solid or stranded [AWG] 18-14 18-14<br />

Control circuit cable connection screw/bolt M3.5 M3.5<br />

Tightening torque [Nm] 1.2 1.2<br />

A66 moellerNA.com STARTER-CAT-USA-1206<br />

For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616