Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
A<br />
Contactors<br />
NEMA/EEMAC Rated Contactors DILM-00N DILM-0N<br />
General<br />
Technical Data<br />
NEMA/EEMAC Rated Contactors<br />
Standards<br />
Lifespan, mechanical<br />
UL, CSA, IEC/EN60947, VDE 0660<br />
AC operated Operations [x 106 ] 10 10<br />
DC operated Operations [x 106 ] 10 10<br />
Max. Operating frequency, mechanical<br />
AC operated [Ops/h] 9000 9000<br />
DC operated<br />
Climatic proofing<br />
[Ops/h] 9000 9000<br />
Open Damp heat constant to IEC60068-2-78<br />
Enclosed<br />
Ambient temperature<br />
Damp heat, cyclic, to IEC60068-2-30<br />
Open [C]<br />
-25 °C…60 °C<br />
-25 °C…60 °C<br />
[F]<br />
-13 °F…140 °F<br />
-13 °F…140 °F<br />
Enclosed [C]<br />
-25 °C…40 °C<br />
-25 °C…40 °C<br />
[F]<br />
-13 °F…104 °F<br />
-13 °F…104 °F<br />
Storage [C]<br />
-40 °C…80 °C<br />
-40 °C…80 °C<br />
Mounting position<br />
AC and DC<br />
Mechanical shock resistance (IEC/EN 60068-2-27)<br />
Half-sinusoidal shock, 10 ms<br />
[F]<br />
-40 °F…176 °F<br />
-40 °F…176 °F<br />
Main Contacts NO contacts Make [g] 10 10<br />
NO/NC contacts Make/Break [g] – –<br />
Auxiliary contacts NO contacts Make [g] 7 7<br />
NC contacts Break [g] 5 5<br />
Degree of protection IP20 IP20<br />
Protection against direct contact when actuated from front (IEC536)<br />
Weight<br />
Finger and-back-of-hand proof<br />
AC [kg] 0.23 0.23<br />
DC<br />
Main terminals<br />
[kg] 0.28 0.28<br />
Wire Capacity minimum [AWG] 18 AWG (single or double) 18 AWG (single or double)<br />
(Cu cable)<br />
Main cable cross sections<br />
maximum [AWG] 14 AWG (single or double) 14 AWG (single or double)<br />
Solid [mm2 ] 1 x (0.75-4.0) 1 x (0.75-4.0)<br />
Flexible <strong>with</strong> ferrule [mm2 ] 1 x (0.75-2.5)<br />
1 x (0.75-2.5)<br />
2 x (0.75-2.5)<br />
2 x (0.75-2.5)<br />
Flexible <strong>with</strong> cable lug [mm2 ] – –<br />
Stranded [mm2 ] – –<br />
Stranded <strong>with</strong> cable lug [mm2 ] – –<br />
Flat conductor Number of segments x width x thickness [mm] – –<br />
Bus bar Width [mm] – –<br />
Main cable connection screw/bolt M3.5 M3.5<br />
Tightening torque<br />
Control circuit cable cross sections<br />
[Nm] 1.2 1.2<br />
Solid [mm2 ] 1 x (0.75-4.0)<br />
1 x (0.75-4.0)<br />
2 x (0.75-2.5)<br />
2 x (0.75-2.5)<br />
Flexible <strong>with</strong> ferrule [mm2 ] 1 x (0.75-2.5)<br />
1 x (0.75-2.5)<br />
2 x (0.75-2.5)<br />
2 x (0.75-2.5)<br />
Solid or stranded [AWG] 18-14 18-14<br />
Control circuit cable connection screw/bolt M3.5 M3.5<br />
Tightening torque [Nm] 1.2 1.2<br />
A66 moellerNA.com STARTER-CAT-USA-1206<br />
For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616