AC-3 Normal Switching Duty (DILM185 – DILM1000)<br />

Rated output of three-phase motors 50 – 60 Hz<br />

kW<br />

560<br />

450<br />

400<br />

355<br />

315<br />

250<br />

200<br />

160<br />

132<br />

110<br />

90<br />

75<br />

55<br />

45<br />

37<br />

30<br />

22<br />

18.5<br />

15<br />

11<br />

7.5<br />

kW<br />

Rated operational current Ie 50 – 60 Hz<br />

A<br />

1000 DILM1000<br />

820 DILM820<br />

750 DILM750<br />

650 DILM650<br />

580 DILM580<br />

500 DILM500<br />

400 DILM400<br />

300 DILM300<br />

250 DILM250<br />

225 DILM225<br />

185 DILM185<br />

145<br />

104<br />

85<br />

72<br />

58<br />

43<br />

36<br />

30<br />

23<br />

16<br />

355 656<br />

315<br />

576 DILM750<br />

280<br />

250<br />

200<br />

512<br />

456<br />

360<br />

DILM650<br />

DILM580<br />

DILM500<br />

160<br />

296 DILM400<br />

132 240<br />

110<br />

90<br />

75<br />

55<br />

45<br />

37<br />

30<br />

22<br />

18.5<br />

15<br />

11<br />

7.5<br />

5.5<br />

4<br />

3<br />

2.2<br />

1.5<br />

200<br />

164<br />

140<br />

104<br />

85<br />

72<br />

58<br />

43<br />

36<br />

30<br />

23<br />

16<br />

12<br />

8.8<br />

6.5<br />

5<br />

3.5<br />

AC-3/400 V<br />

0.01 0.02 0.04 0.06 0.1 0.2 0.4 0.6 0.75 1 2 3 4 5 6 8 10<br />

DILM300<br />

DILM250<br />

DILM225<br />

DILM185<br />

Component lifespan [millions of operations]<br />

AC-4 Extreme Switching Duty (DILM185 – DILM820)<br />

Rated output of three-phase motors 50 – 60 Hz<br />

Rated operational current Ie 50 – 60 Hz<br />

A<br />

DILM820<br />

AC-4/400 V<br />

0.01 0.02 0.03 0.04 0.06 0.1 0.2 0.3 0.4 0.6 1 2 3 4 5 6 8 10<br />

Component lifespan [millions of operations]<br />

Utilization Curves<br />

DIL M Contactors<br />

Squirrel-Cage Motors<br />

Operating Characteristics:<br />

<strong>Start</strong>ing: from rest<br />

Stopping: after attaining full running speed<br />

Electrical Characteristics:<br />

Make: up to 6 x rated motor current<br />

Break: up to 1 x rated motor current<br />

Utilization Category:<br />

100% AC-3<br />

Typical Applications:<br />

Compressors Elevators<br />

Pumps Escalators<br />

Fans Conveyor Belts<br />

Hinged Flaps Bucket-elevators<br />

Mixers Agitators<br />

Centrifuges Air-conditioning Systems<br />

General drives in manufacturing and processing machines<br />

Squirrel-Cage Motors<br />

Operating Characteristics:<br />

Jogging, plugging, reversing<br />

Electrical Characteristics:<br />

Make: up to 6 x rated motor current<br />

Break: up to 6 x rated motor current<br />

Utilitzation Category:<br />

100% AC-4<br />

Typical Applications:<br />

Printing Presses Wire Drawing<br />

Centrifuges<br />

Special drives for manufacturing and processing machines<br />

STARTER-CAT-USA-1206 moellerNA.com A37<br />

For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616<br />