Contactors<br />
DILM185 – DILM1000 Contactors DILM185 DILM225 DILM250 DILM300<br />
Magnet System<br />
Voltage tolerance<br />
AC operated Pick-up x V coil [x Uc] 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min…<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
Dual Voltage Coil 50Hz, 60Hz<br />
or Single Voltage Coil 50Hz<br />
Pick-up x V coil [x Uc] 0.7 x Uc min…<br />
1.15 x Uc max<br />
0.7 x Uc min…<br />
1.15 x Uc max<br />
0.7 x Uc min…<br />
1.15 x Uc max<br />
0.7 x Uc min…<br />
1.15 x Uc max<br />
Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
Dual Frequency Coil 50/60Hz Pick-up<br />
Drop-out<br />
x V coil<br />
x V coil<br />
[x Uc]<br />
[x Uc]<br />
–<br />
–<br />
–<br />
–<br />
–<br />
–<br />
–<br />
–<br />
DC operated ➊ Pick-up x V coil [x Uc] 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min…<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
1.15 x Uc max<br />
Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
0.6 Uc max<br />
Power consumption of the coil in a cold state and 1.0 X Uc<br />
AC operated<br />
Dual Voltage Coil 50Hz, 60Hz pick-up<br />
[VA]<br />
–<br />
–<br />
–<br />
–<br />
sealed<br />
[VA/W]<br />
–<br />
–<br />
–<br />
–<br />
Single Voltage Coil 50Hz pick-up<br />
[VA]<br />
380<br />
380<br />
450<br />
450<br />
sealed<br />
[VA/W] 4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
Single Voltage Coil 60Hz pick-up<br />
[VA]<br />
380<br />
380<br />
450<br />
450<br />
sealed<br />
[VA/W] 4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
Dual Frequency Coil 50/60Hz pick-up<br />
[VA]<br />
380<br />
380<br />
450<br />
450<br />
sealed<br />
[VA/W] 4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
4.3/3.3<br />
DC operated ➊ pick-up<br />
[W]<br />
170<br />
170<br />
170<br />
350<br />
sealed<br />
[W]<br />
4.3<br />
4.3<br />
4.3<br />
4.3<br />
Duty factor DF [% DF] 100 100 100 100<br />
Switching times at 100% Uc (rated coil voltage) main contacts<br />
AC operated Closing delay Min./Max. [ms] < 100<br />
< 100<br />
< 80<br />
< 80<br />
Opening delay Min./Max. [ms]<br />
< 80<br />
< 80<br />
< 80<br />
< 80<br />
DC operated ➊ Closing delay Min./Max. [ms] < 100<br />
< 100<br />
< 80<br />
< 80<br />
Opening delay Min./Max. [ms]<br />
< 80<br />
< 80<br />
< 80<br />
< 80<br />
Arcing time (AC) Maximum [ms]<br />
Permissible contact resistance<br />
(of the external command device <strong>with</strong> actuation of A11)<br />
[mΩ]