A<br />

Contactors<br />

DILM185 – DILM1000 Contactors DILM185 DILM225 DILM250 DILM300<br />

Magnet System<br />

Voltage tolerance<br />

AC operated Pick-up x V coil [x Uc] 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min…<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

Dual Voltage Coil 50Hz, 60Hz<br />

or Single Voltage Coil 50Hz<br />

Pick-up x V coil [x Uc] 0.7 x Uc min…<br />

1.15 x Uc max<br />

0.7 x Uc min…<br />

1.15 x Uc max<br />

0.7 x Uc min…<br />

1.15 x Uc max<br />

0.7 x Uc min…<br />

1.15 x Uc max<br />

Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

Dual Frequency Coil 50/60Hz Pick-up<br />

Drop-out<br />

x V coil<br />

x V coil<br />

[x Uc]<br />

[x Uc]<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

–<br />

DC operated ➊ Pick-up x V coil [x Uc] 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min… 0.7 x Uc min…<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

1.15 x Uc max<br />

Drop-out x V coil [x Uc] 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min… 0.2 x Uc min…<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

0.6 Uc max<br />

Power consumption of the coil in a cold state and 1.0 X Uc<br />

AC operated<br />

Dual Voltage Coil 50Hz, 60Hz pick-up<br />

[VA]<br />

–<br />

–<br />

–<br />

–<br />

sealed<br />

[VA/W]<br />

–<br />

–<br />

–<br />

–<br />

Single Voltage Coil 50Hz pick-up<br />

[VA]<br />

380<br />

380<br />

450<br />

450<br />

sealed<br />

[VA/W] 4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

Single Voltage Coil 60Hz pick-up<br />

[VA]<br />

380<br />

380<br />

450<br />

450<br />

sealed<br />

[VA/W] 4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

Dual Frequency Coil 50/60Hz pick-up<br />

[VA]<br />

380<br />

380<br />

450<br />

450<br />

sealed<br />

[VA/W] 4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

4.3/3.3<br />

DC operated ➊ pick-up<br />

[W]<br />

170<br />

170<br />

170<br />

350<br />

sealed<br />

[W]<br />

4.3<br />

4.3<br />

4.3<br />

4.3<br />

Duty factor DF [% DF] 100 100 100 100<br />

Switching times at 100% Uc (rated coil voltage) main contacts<br />

AC operated Closing delay Min./Max. [ms] < 100<br />

< 100<br />

< 80<br />

< 80<br />

Opening delay Min./Max. [ms]<br />

< 80<br />

< 80<br />

< 80<br />

< 80<br />

DC operated ➊ Closing delay Min./Max. [ms] < 100<br />

< 100<br />

< 80<br />

< 80<br />

Opening delay Min./Max. [ms]<br />

< 80<br />

< 80<br />

< 80<br />

< 80<br />

Arcing time (AC) Maximum [ms]<br />

Permissible contact resistance<br />

(of the external command device <strong>with</strong> actuation of A11)<br />

[mΩ]