18.11.2012 Views

Start with Moeller - Klockner Moeller Parts

Start with Moeller - Klockner Moeller Parts

Start with Moeller - Klockner Moeller Parts

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Technical Data<br />

DIL K Capacitor Switching Contactors<br />

DILK Capacitor Switching Contactors DILK12 DILK20 DILK25 DILK33 DILK50<br />

Magnet System<br />

Voltage tolerance<br />

AC operated Pick-up x V coil [x Uc] 0.8-1.1 0.8-1.1 0.8-1.1 0.8-1.1 0.8-1.1<br />

Drop-out x V coil [x Uc] 0.3-0.6 0.3-0.6 0.3-0.6 0.3-0.6 0.3-0.6<br />

Dual Voltage Coil 50Hz, 60Hz Pick-up x V coil [x Uc] 0.8-1.1 0.8-1.1 0.8-1.1 0.8-1.1 0.8-1.1<br />

or Single Voltage Coil 50Hz Drop-out x V coil [x Uc] 0.3-0.6 0.3-0.6 0.3-0.6 0.3-0.6 0.3-0.6<br />

Dual Frequency Coil 50/60Hz Pick-up x V coil [x Uc] – – – – –<br />

Drop-out x V coil [x Uc] – – – – –<br />

DC operated ➊ Pick-up x V coil [x Uc] 0.8-1.1 ➋ 0.7-1.2 ➌ 0.7-1.2 ➌ 0.7-1.2 ➌ 0.7-1.2 ➌<br />

Drop-out x V coil [x Uc] 0.15-0.6 0.15-0.6 0.15-0.6 0.15-0.6 0.15-0.6<br />

Power consumption of the coil in a cold state and 1.0 X Uc<br />

AC operated<br />

Dual Voltage Coil 50Hz, 60Hz pick-up [VA]<br />

sealed [VA/W]<br />

Single Voltage Coil 50Hz pick-up [VA] 24 52 52 149 149<br />

sealed [VA/W] 3.4/1.2 7.1/2.1 7.1/2.1 16/4.6 16/4.6<br />

Single Voltage Coil 60Hz pick-up [VA] 30 67 67 178 178<br />

sealed [VA/W] 4.4/1.4 8.7/2.6 8.7/2.6 19/5.3 19/5.3<br />

Dual Frequency Coil 50/60Hz pick-up [VA] 25-27 58-62 58-62 154- 168 154- 168<br />

sealed [VA/W] 3.3-4.2 / 1.2-1.4 6.5-9.1 / 2-2.5 6.5-9.1 / 2-2.5 14-22 / 4.3-5.3 14-22 / 4.3-5.3<br />

DC operated ➊ pick-up [W] 4.5 12 AT 24V 12 AT 24V 12 AT 24V 12 AT 24V<br />

sealed [W] 4.5 0.5 AT 24V 0.5 AT 24V 0.5 AT 24V 0.5 AT 24V<br />

Duty factor DF [% DF] 100 100 100 100 100<br />

Switching times at 100% Uc (rated coil voltage) main contacts<br />

AC operated Closing delay Min./Max. [ms] 15-21 16-22 16-22 12-18 12-18<br />

Opening delay Min./Max. [ms] 9-18 8-14 8-14 8-13 8-13<br />

DC operated ➊ Closing delay Min./Max. [ms] 31 47 47 54 54<br />

Opening delay Min./Max. [ms] 12 30 30 24 24<br />

Arcing time (AC) Maximum [ms] 10 10 10 10 10<br />

Electromagnetic Compatibility (EC)<br />

Emitted interference to EN 60947-1<br />

Noise immunity to EN 60947-1<br />

➊ True DC voltage or derived from a full wave 3-phase bridge rectifier or filtered<br />

1-phase AC supply.<br />

➋ At 24V: 0.7…1.3 <strong>with</strong>out additional auxiliary contact modules and ambient<br />

temperature 40 °C<br />

➌ RDC 24 (Uc min 24V DC, Uc max 27V DC)<br />

RDC 60 (Uc min 48V DC, Uc max 60V DC)<br />

RDC 130 (Uc min 110V DC, Uc max 130V DC)<br />

RDC 240 (Uc min 200V DC, Uc max 240V DC)<br />

i.e.: Uc = 0.7 x Uc min - 1.2 x Uc max<br />

Uc = 0.7 x 24V = 16.8 V DC - 1.2 x 27V = 32.4V DC<br />

STARTER-CAT-USA-1206 moellerNA.com A75<br />

For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616<br />

A<br />

Contactors