Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
B<br />
Motor Protection<br />
Current Sensors ZEV-XSW-25 ZEV-XSW-65 ZEV-XSW-145 ZEV-XSW-820<br />
General<br />
Standards IEC/EN 60947, VDE 0660, UL, CSA<br />
Climatic proofing<br />
Ambient temperature<br />
Damp heat, constant, to IEC 60068-2-78; Damp heat, cyclic, to IEC 60068-2-30<br />
Open [°C] -25…60 °C<br />
-25…60 °C<br />
-25…60 °C<br />
-25…60 °C<br />
[°F] -13…140 °F<br />
-13…140 °F<br />
-13…140 °F<br />
-13…140 °F<br />
Enclosed [°C] -25…40 °C<br />
-25…40 °C<br />
-25…40 °C<br />
-25…40 °C<br />
[°F] -13…104 °F<br />
-13…104 °F<br />
-13…104 °F<br />
-13…104 °F<br />
Storage [°C] -40…80 °C<br />
-40…80 °C<br />
-40…80 °C<br />
-40…80 °C<br />
[°F] -40…176 °F<br />
-40…176 °F<br />
-40…176 °F<br />
-40…176 °F<br />
Temperature compensation Continuous<br />
Mounting position As required<br />
Weight [kg] 0.21 0.37 0.45 0.30<br />
Mechanical shock resistance half-sinusoidal shock 10ms [g] 15 15 15 15<br />
Degree of protection IP20 IP20 IP20 IP20<br />
Protection against direct contact when actuated from front<br />
Main Contacts<br />
Finger and back-of-hand proof<br />
Rated impulse <strong>with</strong>stand voltage Uimp [V AC] ➊ ➊ ➊ 8000<br />
Overvoltage category / pollution degree ➊ ➊ ➊ III/3<br />
Rated insulation voltage Ui [V AC] ➊ ➊ ➊ 1000<br />
Rated operational voltage Ue [V AC] ➊ ➊ ➊ 1000<br />
Safe isolation to VDE 0106 Part 101 and Part 101/A1<br />
Between busbar and sensor [V AC] – – – 500<br />
Overload relay setting range [A] 1 – 25 3 – 65 10 – 145 40 – 820<br />
Short-circuit protection rating maximum fuse With overload relay in conjunction <strong>with</strong> a transformer as required for the contactor<br />
Push-through opening Ø [mm] 6 13 21 110<br />
➊ Dependant on the current wiring that is used.<br />
Technical Data<br />
Current Sensors<br />
B24 moellerNA.com STARTER-CAT-USA-1206<br />
For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616