Motor Protection<br />
> Class 10 overload; trip response from 2 to 10 seconds<br />
> Ambient compensated, bimetallic overload tripping mechanism<br />
> Phase failure sensitive to IEC/EN 60947<br />
> Manual / Automatic reset button<br />
> Built-in NO and NC auxiliary contacts<br />
Direct or Separate Mount Z5 Thermal Overload Relays for DILM185 – DILM250 Contactors<br />
Overload Relay<br />
Adjustable<br />
Setting<br />
Range<br />
(A)<br />
Auxiliary<br />
Contacts<br />
50 – 70 1 1<br />
➊ When directly mounting device observe the maximum permissible fuse of the<br />
contactor.<br />
NO NC For use <strong>with</strong>… Fuses (A)<br />
Short-Circuit<br />
Protection<br />
(Max 600V AC) ➊<br />
Circuit<br />
Breaker (A)<br />
Thermal Overload Relays<br />
Type Z5<br />
Catalog Number Price<br />
250 250 Z5-70/FF250 380<br />
70 – 100 1 1 400 class J 400 Z5-100/FF250 395<br />
95 – 125 1 1<br />
DILM185 – DILM250<br />
500 class J 500 Z5-125/FF250 395<br />
120 – 160 1 1<br />
DIULM185 – DIULM250<br />
600 class J 600 Z5-160/FF250 410<br />
160 – 220 1 1 800 class L 800 Z5-220/FF250 430<br />
200 – 250 1 1 700 class L 600 Z5-250/FF250 430<br />
B8 moellerNA.com Discount Schedule A20<br />
STARTER-CAT-USA-1206<br />
For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616