Contactors<br />

NEMA/EEMAC Rated Contactors DILM-00N DILM-0N<br />

UL/CSA Ratings<br />

Continuous current rating<br />

50/60Hz, 3 pole Open [A] 20 20<br />

Enclosed [A] 18 18<br />

Horsepower ratings (AC)<br />

Single phase 115VAC [HP] 1/3 1<br />

200VAC [HP] – –<br />

230VAC [HP] 1 2<br />

Three phase 200VAC [HP] 1 1/2 3<br />

230VAC [HP] 1 1/2 3<br />

460VAC [HP] 2 5<br />

575VAC [HP] 2 5<br />

NEMA Size (non-joging duty) [Size] 00 0<br />

Current heat loss at Ith Ith [W] 4.7 4.7<br />

Current heat loss at Ie to AC-3/400V Ie [W] 0.6 1.1<br />

Impedence per pole [mΩ] 2.5 2.5<br />

Magnet System<br />

Voltage tolerance<br />

AC operated Pick-up x V coil [x Uc] 0.8-1.1 0.8-1.1<br />

Drop-out x V coil [x Uc] 0.3-0.6 0.3-0.6<br />

Dual Voltage Coil 50Hz, 60Hz Pick-up x V coil [x Uc] 0.8-1.1 0.8-1.1<br />

or Single Voltage Coil 50Hz Drop-out x V coil [x Uc] 0.3-0.6 0.3-0.6<br />

Dual Frequency Coil 50/60Hz Pick-up x V coil [x Uc] – –<br />

Drop-out x V coil [x Uc] – –<br />

DC operated ➊ Pick-up x V coil [x Uc] 0.8-1.1 ➋ 0.8-1.1 ➋<br />

Drop-out x V coil [x Uc] 0.15-0.6 0.15-0.6<br />

Power consumption of the coil in a cold state and 1.0 X Uc<br />

AC operated<br />

Dual Voltage Coil 50Hz, 60Hz pick-up [VA] – –<br />

sealed [VA/W] – –<br />

Single Voltage Coil 50Hz pick-up [VA] 24 24<br />

sealed [VA/W] 3.4/1.2 3.4/1.2<br />

Single Voltage Coil 60Hz pick-up [VA] 30 30<br />

sealed [VA/W] 4.4/1.4 4.4/1.4<br />

Dual Frequency Coil 50/60Hz pick-up [VA] 25-27 25-27<br />

sealed [VA/W] 3.3-4.2 / 1.2-1.4 3.3-4.2 / 1.2-1.4<br />

DC operated ➊ pick-up [W] 3 4.5<br />

sealed [W] 3 4.5<br />

Duty factor DF [% DF] 100 100<br />

Switching times at 100% Uc (rated coil voltage) main contacts<br />

AC operated Closing delay Min./Max. [ms] 15-21 15-21<br />

Opening delay Min./Max. [ms] 9-18 9-18<br />

DC operated ➊ Closing delay Min./Max. [ms] 31 31<br />

Opening delay Min./Max. [ms] 12 12<br />

Arcing time (AC) Maximum [ms] 10 10<br />

Permissible residual current (<strong>with</strong> actuation of A11 by the electronics <strong>with</strong> no signal) [mA] – –<br />

Electromagnetic Compatibility (EC)<br />

Emitted interference to EN 60947-1<br />

Noise immunity to EN 60947-1<br />

➊ True DC voltage or derived from a full wave 3-phase bridge rectifier or filtered<br />

1-phase AC supply.<br />

Technical Data<br />

NEMA/EEMAC Rated Contactors<br />

➋ At 24V: 0.7…1.3 <strong>with</strong>out additional auxiliary contact modules and ambient<br />

temperature 40 °C<br />