The full-load current values listed in the table below are for motors<br />

running at usual speeds, <strong>with</strong> normal torque characteristics at 1.15<br />

service factor. This table is a guide only. The actual full load motor<br />

amps for your motor may be different than the average values<br />

listed here. Always use the actual motor current listed on the motor<br />

nameplate when purchasing motor control and protection products.<br />

Motor<br />

Rating (HP)<br />

115 V<br />

AC Induction Motor – Full Load Current (A)<br />

Single Phase Three Phase<br />

200 V 230 V 200 V 230 V 460 V 575 V<br />

1/6 4.4 2.5 2.2 – – – –<br />

1/4 5.8 3.3 2.9 – – – –<br />

1/3 7.2 4.1 3.6 – – – –<br />

1/2 9.8 5.6 4.9 2.3 2.0 1.0 0.8<br />

3/4 13.8 7.9 6.9 3.2 2.8 1.4 1.1<br />

1 16 9.2 8 4.1 3.6 1.8 1.4<br />

1-1/2 20 11.5 10 6.0 5.2 2.6 2.1<br />

2 24 13.8 12 7.8 6.8 3.4 2.7<br />

3 34 19.6 17 11.0 9.6 4.8 3.9<br />

5 56 32.2 28 17.5 15.2 7.6 6.1<br />

7-1/2 80 46 40 25.3 22 11 9<br />

10 100 57.5 50 32.2 28 14 11<br />

15 – – – 48.3 42 21 17<br />

20 – – – 62.1 54 27 22<br />

25 – – – 78.2 68 34 27<br />

30 – – – 92.0 80 40 32<br />

40 – – – 119.6 104 52 41<br />

50 – – – 149.5 130 65 52<br />

60 – – – 177.1 154 77 62<br />

75 – – – 220.8 192 96 77<br />

100 – – – 285.2 248 124 99<br />

125 – – – 358.8 312 156 125<br />

150 – – – 414 360 180 144<br />

200 – – – 552 480 240 192<br />

300 – – – 825 720 360 288<br />

350 – – – 963 840 420 336<br />

400 – – – 1100 960 480 384<br />

450 – – – 1238 1080 540 432<br />

500 – – – 1375 1200 600 480<br />

600 – – – 1650 1440 720 576<br />

700 – – – 1925 1680 840 672<br />

800 – – – 2200 1920 960 768<br />

900 – – – 2475 2160 1080 864<br />

1000 – – – 2750 2400 1200 960<br />

NOTE: This chart was developed from Table 430-148 & 430-150 of the NEC, Table 52.2 of UL standard 508 and<br />

from the Canadian Electrical Code (CEC), Part 1, table 44 and 45.<br />

STARTER-CAT-USA-1206 moellerNA.com A7<br />