A<br />

Contactors<br />

Auxiliary Contacts …DILE(M)<br />

General<br />

DILA-XHI<br />

DILM32-XHI DILM150-XHI DILM1000-XHI<br />

UL/CSA Pilot duty rating [AC] – A600 - 10A 600V A600 - 15A 600V A600 - 15A 600V<br />

general use<br />

general use<br />

general use<br />

[DC] – P300 - 1A 250V general use<br />

Positively guided contacts <strong>with</strong>in an auxiliary contact module<br />

(to IEC60947-5-1 Annex L) does not apply to early make - late break contacts.<br />

– Yes Yes Yes<br />

Break contact (not late break contact) suitable as a mirror contact<br />

(to IEC/EC 60947-4-1 Annex F)<br />

– Yes Yes Yes<br />

Interlocked opposing contacts to ZH 1 / 457, including auxiliary contact<br />

module (not late break contact)<br />

Yes – – –<br />

Rated Impulse <strong>with</strong>stand voltage Uimp [VAC] 6000 6000 6000 6000<br />

Overvoltage category/pollution degree III/3 III/3 III/3 III/3<br />

Rated (insulation) voltage - IEC Ui [VAC] 690 690 690 690<br />

Rated operational voltage - IEC Ue [VAC] 600 500 500 500<br />

Safe isolation to VDE 0106 Part 101 and Part 101/A1<br />

Between coil and auxiliary contacts [VAC] 300 400 440 440<br />

Between the auxiliary contacts [VAC} 300 400 440 440<br />

IEC 974 Operating Current Ie<br />

AC-15 220…240V Ie [A] 6/4 – – –<br />

230V Ie [A] – 6 6 6<br />

380…415V Ie [A] 3/2 4 4 4<br />

500V Ie [A] 1.5/1.5 1.5 1.5 1.5<br />

DC-13 ➊ L/R ≤ 15 ms 24V Ie [A] 2.5 10 10 10<br />

Single contact 60V Ie [A] – 6 6 6<br />

110V Ie [A] – 3 3 3<br />

220V Ie [A] – 1 1 1<br />

Contacts in series 2 60V Ie [A] 2.5 – – –<br />

3 110V Ie [A] 1.5 – – –<br />

3 220V Ie [A] 0.5 – – –<br />

Conventional thermal current Ith [A] 10 10 15 15<br />

Control circuit reliability ➋ Failure rate [Ops] Less than (1) one failure at 100 million operations<br />

Component lifespan at Ue = 230V, AC-15, 3A Ops [x 10 6 ] 0.2 1.3 1.3 1.3<br />

DC-13 ➌ L/R = 50ms: 2 contacts in series at Ie=0.5A Ops [x 10 6 ] 0.15 – – –<br />

Short-circuit rating <strong>with</strong>out welding<br />

Maximum overcurrent protective device PKZM0-4 – – –<br />

Maximum fuse 500V [A gG/gL] 6 10 16 16<br />

500V [A fast] 10 – – –<br />

Current heat loss at conventional free air thermal current<br />

Per contact Ith [W] 0.2 0.2 – –<br />

➊ Making and breaking conditions to DC-13, time L/R constant as stated.<br />

➋ At Ue = 24V DC, Umin = 17V, Imin = 5.4mA<br />

Technical Data<br />

Auxiliary Contacts<br />

➌ True DC voltage or derived from a full wave 3-phase bridge rectifier or filtered<br />

1-phase AC supply.<br />

A62 moellerNA.com STARTER-CAT-USA-1206<br />

For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616