Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
Start with Moeller - Klockner Moeller Parts
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
A<br />
Contactors<br />
DILEM – DILM150 Contactors DILEM(4) DILMP20 DILM7 DILM9 DILM12 DILM17<br />
UL/CSA Ratings<br />
Continuous current rating<br />
50/60Hz, 3 pole Open [A] – 20 20 20 20 35<br />
Enclosed [A] – 18 18 18 18 32<br />
Full load amperes<br />
1 - pole 115V [A] – – 5.8 9.8 9.8 16<br />
1 - pole 200V [A] – – 7.9 9.2 11.5 13.8<br />
1 - pole 230V [A] – – 8 10 12 17<br />
3 - pole 230V [A] – – 6.8 9.6 9.6 15.2<br />
3 - pole 480V [A] – – 4.8 7.6 14 14<br />
3 - pole 600V [A] – – 6.1 9 11 17<br />
Locked rotor amperes<br />
3 - pole 230V [A] – – 50 64 64 92<br />
3 - pole 480V [A] – – 32 46 81 81<br />
3 - pole 600V [A] – – 36.8 50.8 64.8 93<br />
Horsepower ratings (AC)<br />
Single phase 115VAC [HP] 1/2 1/2 1/4 1/2 1 2<br />
200VAC [HP] 1 1 3/4 1 2 2<br />
230VAC [HP] 1 1/2 1 1/2 1 1 1/2 2 3<br />
Three phase 200VAC [HP] 2 3 1 1/2 3 3 7 1/2<br />
230VAC [HP] 3 3 2 3 3 7 1/2<br />
460VAC [HP] 5 5 3 5 10 10<br />
575VAC [HP] 5 7 1/2 5 7 1/2 10 15<br />
Horsepower ratings (DC)<br />
3 - pole break 125VDC Ie [HP] – 3/4 1/4 1/2 3/4 2<br />
250VDC Ie [HP] – 2 1 1 1/2 2 3<br />
Lighting ratings<br />
3 - pole break Electrical discharge lamps (Ballast) [A] – – 20 20 20 40<br />
3 - pole break Incandescent lamps (Tungsten) [A] – – 14 14 14 40<br />
Resistance heating ratings<br />
3 - pole break [A] – – 20 20 20 40<br />
Refrigeration ratings<br />
3 - pole break [A] – – 10 10 10 30<br />
Elevator ratings<br />
200V [A] – – 3.7 7.8 7.8 11<br />
240V [A] – – 6.0 6.8 9.6 9.6<br />
480V [A] – – 3.4 4.8 11.0 11<br />
600V [A] – – 3.9 6.1 9.0 11<br />
200V [HP] – – 3/4 2 2 3<br />
240V [HP] – – 1 1/2 2 3 3<br />
480V [HP] – – 2 3 7 1/2 7 1/2<br />
600V [HP] – – 3 5 7 1/2 10<br />
IEC (AC) Application Ratings<br />
AC 1 - Duty<br />
Open 40 °C / 104 °F Ith [A] 22 22 22 22 22 40<br />
Conventional free air 50 °C / 122 °F Ith [A] 20 21 21 21 21 38<br />
Thermal current, 55 °C / 137 °F Ith [A] 19 21 21 21 21 37<br />
3-pole, 50-60Hz 60 °C / 140 °F Ith [A] – 20 20 20 20 35<br />
Enclosed ➊ Ith [A] 16 18 18 18 18 32<br />
Conventional free air<br />
Thermal current,<br />
Open ➊ Ith [A] 50 50 50 50 50 85<br />
1-pole, 50-60Hz Enclosed ➊ Ith [A] 40 45 45 45 45 80<br />
➊ At maximum permissible ambient temperature.<br />
Technical Data<br />
DIL EM to DIL M150 Contactors<br />
A44 moellerNA.com STARTER-CAT-USA-1206<br />
For Immediate Delivery call KM<strong>Parts</strong>.com at (866) 595-9616