UMV multicone dynamic bonded anchor<br />

Chemical fixings<br />

LOADS<br />

UMV multicone dynamic<br />

Highest permissible loads for a single anchor 1) 6) in concrete B25 resp. C20/25 4)<br />

For the design the complete approval Z-21.3-1662 has to be considered.<br />

Type<br />

Cracked concrete<br />

Non-cracked concrete<br />

Effective Min. Installation Permissible Permissible Min. Min. Permissible Permissible Min. Min.<br />

anchorage member torque tensile load shear load spacing edge tensile load shear load spacing edge<br />

depth thickness<br />

distance<br />

distance<br />

h ef h min T inst<br />

3)<br />

∆N zul<br />

3)<br />

∆V zul<br />

2)<br />

s min<br />

2)<br />

c min<br />

3)<br />

∆N zul<br />

3)<br />

∆V zul<br />

2)<br />

s min<br />

2)<br />

c min<br />

[mm] [mm] [Nm] [kN] [kN] [mm] [mm] [kN] [kN] [mm] [mm]<br />

UMV-A dyn M12 x 100 100 200 40,0 11,7 5,6 100 100 12,2 5,6 100 100<br />

UMV-A dyn M16 x 125 125 250 60,0 14,8 6,7 130 130 14,8 6,7 130 130<br />

UMV-A dyn M20 x 170 170 340 100,0 25,0 16,3 170 170 34,9 16,3 170 170<br />

UMV-A dyn M24 x 220 220 440 120,0 35,8 16,3 220 220 38,5 16,3 220 220<br />

1)<br />

The permissible loads apply for the design method II (unknown lowest load and unknown load<br />

cycles). The partial safety factor for material resistance and the partial safety factor for action<br />

regarding fatigue as regulated in the approval are considered. When using design method I higher<br />

permissible loads may be possible. As an single anchor counts e.g. an anchor with a spacing s ≥<br />

3 x h ef and an edge distance c ≥ 1,5 x h ef . Accurate data see approval.<br />

2)<br />

Minimum possible axial spacings resp. edge distance while reducing the permissible load.<br />

3)<br />

For combinations of tensile loads, shear loads as well as reduced edge distances or spacings<br />

(anchor groups) see approval.<br />

4)<br />

For higher concrete strength classes up to C50/60 higher permissible loads may be possible.<br />

6)<br />

The given loads are valid for fixations in dry and humid concrete for temperatures in the substrate<br />

up to +50°C (resp. short term up to 80°C) and best possible drillhole cleaning according approval.<br />

134