Universal frame fixing FUR<br />

Frame fixings / Stand-off installation<br />

LOADS<br />

Universal frame fixing FUR 4)<br />

Highest permissible loads 1) for a single anchor for multiple fixings of facades in masonry.<br />

For the design the complete approval Z-21.2-1204 has to be considered.<br />

Solid brick masonry and perforated brick masonry<br />

Type<br />

Compressive<br />

brick strength<br />

Brick type,<br />

naming acc. DIN<br />

Min.<br />

embedment depth<br />

Min.<br />

member thickness<br />

Permissible load Min.<br />

spacing<br />

Min.<br />

edge distance<br />

f b h nom (h v ) h (d)<br />

3) 5)<br />

F perm s min (a) 2) c min (a r ) 6)<br />

1)<br />

The required safety factors as regulated in the approval are considered.<br />

2)<br />

Minimum permissible spacing without reducing the permissible load.<br />

3)<br />

Valid for tensile load, shear load and oblique load under any angle. Restrictions for permanently<br />

acting tensile loads see approval. For combinations of tensile loads, shear loads, bending<br />

moments see approval table 4.<br />

4)<br />

gvz and A4. For exterior applications of galvanised screws measures against incoming humidity<br />

have to be taken.<br />

[N/mm²] [-] [mm] [mm] [kN] [mm] [mm]<br />

Solid brick Mz<br />

FUR 8 ≥ 12 Mz 70 115 0,60 100 100<br />

FUR 10 ≥ 12 Mz 70 115 0,80 100 100<br />

FUR 14 ≥ 12 Mz 70 115 0,80 250 100<br />

Solid sand-lime brick and solid block KS<br />

FUR 8 ≥ 12 KS 70 115 0,60 100 100<br />

FUR 10 ≥ 12 KS 70 115 0,80 100 100<br />

FUR 14 ≥ 12 KS 70 115 0,80 250 100<br />

Vertically perforated brick Hlz<br />

FUR 8 ≥ 12 HLz 70 115 - 100 100<br />

FUR 10 ≥ 12 HLz 70 115 0,3 7) 250 100<br />

FUR 14 ≥ 12 HLz 70 115 0,5 7) 250 100<br />

Perforated sand-lime brick KSL<br />

FUR 8 ≥ 6 KSL 70 115 - 100 100<br />

FUR 10 ≥ 6 KSL 70 115 0,40 250 100<br />

FUR 14 ≥ 6 KSL 70 115 0,60 250 100<br />

Hollow block of lightweight aggregate concrete Hbl<br />

FUR 8 ≥ 2 Hbl 70 8) 115 - 100 100<br />

FUR 10 ≥ 2 Hbl 70 8) 115 0,25 250 100<br />

FUR 14 ≥ 2 Hbl 70 8) 115 0,30 250 100<br />

Solid brick and solid block of lightweight aggregate concrete<br />

FUR 8 ≥ 2 V 70 115 - 100 100<br />

FUR 10 ≥ 2 V 70 115 0,25 100 100<br />

FUR 14 ≥ 2 V 70 115 0,50 250 100<br />

5)<br />

The given values apply for rotary drilling in perforated bricks (without impact).<br />

6)<br />

Minimum permissible edge distance with surcharge as well as to not solidified joints. For edge<br />

distance without surcharge see approval.<br />

7)<br />

Valid for raw density higher than 1,0 kg/dm³. Otherwise the permissible load has to be determined<br />

by tests on site.<br />

8)<br />

The expansion part of the plug must be located in the web of the brick (see approval, appendix 6).<br />

236