<strong>System</strong><strong>pro</strong> M compact ®<strong>Technical</strong> <strong>details</strong>Accessories for measurementinstrumentsMeasurementdevicesFAULT CURVESF %543210-1-2-3-4-5-6-7-8-9-10-11-12-13-14-15Rated currentOvercurrent in <strong>pro</strong>tection transformersOvercurrent in measurementtransformers up to Sf 5NxRated current0,05 0,1 0,2 1 1,2 2 3 4 5 6 7 8 9 10Magnetic saturationFs 5 10 P5 10 P10Curve at 1/4 of rated impedanceRated impedance curveCable diameter calculationThe following formula applies for determining the diameters of a 95 mm 2 cable:- section=rxrx3.14 that is r 2 x3.14 from which r=√ section/3.14 r=√ 95/3.14=30.25=5.5 mm, so theradius is 5.5 mm- diameter=r+r so the diameter is 5.5+5.5 mm=11 mm (copper diameter to be added to the insulatingmaterial thickness, total ø about 20 mm).With many insertion of the cable into the current transformer it is possible to halve the primary currentwhile performance and rating values remain unaltered.Example11ABB11/105