<strong>System</strong><strong>pro</strong> M compact ®<strong>Technical</strong> <strong>details</strong>Functions and classifi cation criteriafor RCDsRCDsB type RCDs are recommended for use with drives and inverters for supplying motors for pumps,lifts, textile machines, machine tools, etc., since they recognise a continuous fault current with a lowlevel ripple.Type AC and type A RCDs comply with IEC/EN 61008/61009, whilst type B RCDs are not yet coveredby any reference Standard for the household and similar use. Type B is covered only by IEC/EN60947-2 for low voltage switchgear and control gear and by IEC/EN 60755 for residual currentoperated <strong>pro</strong>tective devices.According to tripping sensitivity (IΔn value), RCDs may be divided into the following categories:• low-sensitivity (IΔn >0.03 A), not suitable for <strong>pro</strong>tection against direct contacts; co-ordinatedwith the earth system according to the formula IΔn