12.07.2015 Views

Technical details System pro M compact®

Technical details System pro M compact®

Technical details System pro M compact®

SHOW MORE
SHOW LESS
  • No tags were found...

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

<strong>System</strong><strong>pro</strong> M compact ®<strong>Technical</strong> <strong>details</strong>Performances at different ambienttemperatures, altitudes and frequenciesMCBs2. Multiply the rated current (equivalent) referring to the new temperature by another factor0.9 only for loads that last for more than an hour.3. Multiply the rated current (equivalent) referring to the new temperature by another factoronly in case of presence of several devices installed alongside each other; see table.Influence of adjacent devices1.00.9Fm Factor0.80.70.61 2 3 4 5 6 7 8 9Number of devicesOEPM0108Influence of adjacent devicesCorrection factor FmNo. of adjacent devices Fm1 12 0.953 0.94 0.865 0.826 0.7957 0.788 0.779 0.76>9 0.76Example: S 202 C 16 with T=35 °CType of use Values to use Formula Calculation ResultLoad less than an hour In (amb. t°) -see tables- In=15.43 ALoad more than an hour In (amb. t°) -see tables-, 0.9 In (amb. t°)x0.9 15.43x0.9 In=13.9 ALoad over an hour with 8 adj.devices In (amb. t°) -see tables-, 0.9, Fm (0.77) In (amb. t°)x0.9x0.77 15.43x0.9x0.77 In=10.7 A1111/54 ABB

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!