<strong>System</strong><strong>pro</strong> M compact ®<strong>Technical</strong> <strong>details</strong>E 259 installation relaysCommanddevicesE 259 INSTALLATION RELAYSInformation about lamp insertion between phase and neutralIncandescent lampsPower [W][Number of lamps]15 12025 7240 4560 3075 24100 18150 12200 9300 6500 3Fluorescent lamps without power factor capacitors or serial compensatedPower [W][Number of lamps]1518 5020 4530 3036 2540 2358 1665 13Fluorescent twin-lampsPower [W][Number of lamps]2x18 502x20 452x30 302x36 252x40 232x58 162x65 1311Fluorescent lamps with power factor capacitors in parallelPower [W][Number of lamps]18 1720 1730 1436 1340 1258 865 711/92 ABB