Pattern 3Option switchDI-2DI-1External contact(level-triggered)External contact(level-triggered)External contact input to DI-1Short contact : Starts all indoor unit operation.Open contact : Stops all indoor unit operation.External contact input to DI-2Short contact : Disables the use of all wired/wireless remote controllers.Open contact : Enables the use of all wired/wireless remote controllers.Schedule control is not interrupted in Pattern 3.Pattern 4Option switchDI-2DI-1External contact pulse input to DI-1Short pulse-triggered : Starts all indoor unit operation.External contact (pulse-triggered)Duration : 0.5~1.0secExternal contact (pulse-triggered)Duration : 0.5~1.0secIntegrated management systemExternal contact pulse input to DI-2Short pulse-triggered : Stops all indoor unit operation.Schedule control is not interrupted in Pattern 4.109