Temperature control with built-in temperature sensorIndividual control systemTemperature sensor in the wired remote controller can be appliedto all the connected indoor units of DVM Plus II/III.DIP SwitchSW 5SW 6FunctionOFF Use the temperature sensor in the indoor unit.ONOFFONUse the temperature sensor in the wired remote control.Reserved.Use the average value of the temperature sensors in theindoor unit(s) and the wired remote controller(SW5 in ON).Here, the wired remote controller chooses the indoor unitof the lowest MAIN address, or one of the indoor units atrandom.Heating mode temperature compensationDVM Plus III 4way PCBK5DIP SwitchSW 5Function+2°C(3.6°F), +5°C(9°F) temperature compensation.DIP SwitchFunctionSW 5 OFF Use the temperature sensor in the wired remote control.What happens to heating mode temperature compensation [+2°C(3.6°F), +5°C(9°F)] when the use of thewired R/C built-in temperature is enabled ?• The heating mode temperature compensation is cleared. [0°C(0°F)]• If you want to use compensation, set value in the service mode menu 8.15