3 Integrated management system1. DMS (Data Management Server)(7) Option switchDIP switch (SW03) : Use only for external contact signal control.Pattern1DIP switch no.2 3 4<strong>Control</strong> detailsContact input123OFFONOFFOFFOFFONOFFOFFOFFOFFOFFOFFNo function (Default setting)1. Emergency stop / Resume operationAdditional functions are temporarily disabledunder Emergency stop.1. Indoor unit ON/OFF control2. Permitted/Prohibited remote control useAdditional functions are not interrupted.Not appliedLevel-triggeredLevel-triggered4ONONOFFOFF1. Indoor unit ON/OFF controlAdditional functions are not interrupted.Pulse-triggeredPattern 2Option switchDI-2DI-1No functionExternal contact(Level-triggered)Short external contact : Emergency stop• Turns off all the indoor units when there is an ON signal input.• All the remote control use is disabled.• DMS will ignore any request from the upper-layer controllers.• Schedule control is disabled temporarily.Open external contact : Resume operation• After Emergency stop, the indoor units stay in the current OFF states.• All the remote control use is restored to the previous state.• Schedule control is enabled again.74