Control Systems - Uniclima
Control Systems - Uniclima
Control Systems - Uniclima
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Pattern 3Option switchDI-2DI-1External contact(Level-triggered)External contact(Level-triggered)External contact input to DI-1Short contact : Starts all indoor unit operation.Open contact : Stops all indoor unit operation.External contact input to DI-2Short contact : Disables the use of all wired/wireless remote controllers.Open contact : Enables the use of all wired/wireless remote controllers.Schedule control is not interrupted in Pattern 3.Pattern 4Option switchDI-2DI-1External contact pulse input to DI-1Short pulse-triggered : Starts all indoor unit operation.External contact (Pulse-triggered)Duration : 0.5~1.0secExternal contact (Pulse-triggered)Duration : 0.5~1.0secIntegrated management systemExternal contact pulse input to DI-2Short pulse-triggered : Stops all indoor unit operation.Schedule control is not interrupted in Pattern 4.75