Menu Detailed description DisplaySW 8 OFF : Monitor the setting temperaturecompensation value under the Heating mode.SW 8 ON : Set the setting temperature compensationvalue.Setting temperature compensation value of the heating operation:Compensate the setting temperature used for heating operation control.(ex :User setting temperature 30°C(86°F). Heating operationcompensation temperature 5°C(9°F). Heating operation controlbased on the set temperature of 35°C(95°F)Select temperature compensation values :1) 0 – Use indoor unit PCB setting value2) 1 – Use wired remote controller setting valueTemperature compensation : -9~9°C (-16.2~16.2°F)Select temperaturecompensation.Set temperaturecompensation.Individual control systemSW 8 OFF / ON: Monitor if central control is in use.(Check the indoor unit PCB switch setting status)0: Use central control1: No central control usedSW 8 OFF / ON : Monitor if the drain pump is in use.(Check the indoor unit PCB switch setting status)0: Drain pump use1: No drain pump usedSW 8 OFF / ON: Monitor if electric heater is in use.(Check the indoor unit PCB switch setting status)0: Electric heater use1: No electric heater usedSW 8 OFF / ON: Monitor if hot water control is in use.(Check the indoor unit PCB switch setting status)0: Hot water control use1: No hot water control usedSW 8 OFF / ON: Display connected indoor units quantity.SW 8 OFF / ON: Display wired remote controller softwareversion. In case of indoor unit group control, only menu 4, 13, 14 can be available.19