Service mode menu descriptionIndividual control systemPress Hr., Min., and temperature setting buttonfor more than 5 seconds to enter Service mode.Menu Detailed description DisplaySW 8 OFF: Option code monitoringSW 8 ON: Option code settingOption code : Detailed indoor unit functions such as indoor unit modeltype, indoor unit capacity, blackoutrestoration, and drain pump control are set by thecombination of 12-digit or 24-digit numbers.(ex. 0d7800-198091-200001-300000)SW 8 OFF : Indoor unit address monitoringSW 8 ON : Indoor unit address ( RMC address only)settingIndoor unit address:Address used for indoor unit communication andcontrol(Set by a rotary switch of the indoor unit PCB)1) Main address: Indoor unit’s physical address2) RMC address: Address used in the central controlRMC (1) : Interface module channel addressRMC (2) : Indoor unit group addressSW 8 OFF / ON: Monitor indoor unit cycle dataMenuData1 Indoor temperature2 EVA-IN temperature3 EVA-OUT temperature4 EEV stepMain addressMenuLeft: RMC (1) addressRight: RMC (2) addressData17