CAUTION During operation mode lock, if user change operation mode using other controller, then MWR-SH00 lockscurrent new operation mode.HeatIndividual control systemHeatUser locks “Cool” modeUser changesoperation mode to"Heat" using wirelessR/C“Heat” mode lock(1) Indoor unit runs as “Heat”(2) R/C locks current operation mode.Option switchAble to set an additional function in a simple way with 8 optionswitches on the wired remote controller PCB. Default switch settings are all OFF.Switch No. OFF ONSW 1For cooling and heating modelFor cooling model only (If the operation mode is selected,heating operation display is skipped.)SW 2 Temperature display in Celsius (°C). Temperature display in Fahrenheit (°F).SW 3Able to use both wireless remote controller andwired remote controller for indoor unit control.SW 4 Use Auto mode Auto mode skipSW 5Mode lock release in case of power reset orfailureUnable to use wireless remote controller.Automatic mode lock even in case of power reset orfailureSW 6 - -SW 7 - -SW 8If two wired remote controllers are used to control1 indoor unit, it is set as a Master wired remotecontroller.If two wired remote controllers are used to control1 indoor unit, it is set as a Slave wired remote controller.37