<strong>Warrawee</strong> <strong>Substation</strong> Page 14Operational Noise & Construction Noise & Vibration AssessmentReport No. 11332 Version BTable 5-2Predicted Noise Levels at Residential Receivers – L Aeq,15minLocationDistance,(m)Predicted NoiseLevels L Aeq,15minRBL, dBA,Night Time(10pm - 7am)IntrusiveCriteria,Night Time(10pm - 7am)Complies38 Brentwood Ave 57 25 31 36 Yes40 Brentwood Ave 32 30 31 36 Yes51 Brentwood Ave 61 24 31 36 Yes53 Brentwood Ave 69 23 31 36 Yes55 Brentwood Ave 56 25 31 36 Yes57 Brentwood Ave 36 29 31 36 Yes59 Brentwood Ave 32 30 31 36 Yes61 Brentwood Ave 33 28 31 36 Yes63 Brentwood Ave 46 27 31 36 Yes65 Brentwood Ave 70 23 31 36 Yes15 Winton St 40 28 33 38 Yes17 Winton St 36 29 33 38 YesPredicted operational levels <strong>of</strong> <strong>Warrawee</strong> Traction <strong>Substation</strong> are within the ‘Background Noise+ 5dB’ night time criteria and are in most cases within the Background Noise Levels. Hence theoperation <strong>of</strong> the substation complies with the intrusive criteria.