Commissioning GuideP92x/EN CM/F22<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong> Page 13/264.2.7 Voltage inputsThis test verifies the accuracy of voltage measurement is within the acceptable tolerances.4 types of connection are possible for the <strong>MiCOM</strong> <strong>P921</strong>, <strong>P922</strong> and <strong>P923</strong> relays: 3VT (phaseneutral),3VT (phase-phase) + residual VT, 3VT (phase-neutral) + residual VT, 2VT (phasephase)+ residual VT.THE FOLLOWING TESTS ARE PERFORMED WITH A 3VT CONNECTION (PHASE-PHASE) CORRESPONDING TO THE MOST FREQUENT CONFIGURATION.Apply the rated voltage to each voltage input. Check its magnitude using a multimeter. Referto Table 6 for the corresponding reading in the relay's "MEASUREMENTS" menu and recordthe value displayed.MEASUREMENTS menuVoltage applied toVA (RMS value) 41-42VB (RMS value) 43-44VC (RMS value) 45-46TABLE 6: VOLTAGE INPUT TERMINALSThe measured voltage values on the relay will be in primary volts.The measurement accuracy of the relay is ±1%. Nevertheless, additional allowance must bemade for the accuracy of the test equipment being used.