Commissioning GuideP92x/EN CM/F22<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong> Page 15/265.3 Testing the "Phase overvoltage protection" and "Phase undervoltage protection"functions5.3.1 Wiring diagramAuxiliarypower supply +_3334WD373536WatchdogRL1642RL1StopchronoAuxiliarypower supplyA+ _41<strong>MiCOM</strong> P92*RL2RL3121081614RL2RL3VoltagesourceBC42434445RL4RL5201831RL4RL5NSee note 3464950See note 1RL6RL7RL8759111315RL6RL7RL8EL1EL2EL3EL4EL522242628171921232527See note 2*LEDs29303132+_4 programmableLEDs-Case earthRS 485communication port(Modbus, Courier,CEI60870-5-103)Notes :(1) Supplementary hardware for <strong>MiCOM</strong> <strong>P922</strong>-<strong>P923</strong> relay(2) Supplementary hardware for <strong>MiCOM</strong> <strong>P922</strong>-<strong>P923</strong> relay(3) 3VT assembly, Phase-Neutral(* For the last relayof the RS 485 link,connect terminal 30 to terminal 32)P0408ENaFIGURE 2: (V>) AND (V>>) STAGE TEST