Technical GuideP92x/EN TD/H42Technical Data<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong> Page 27/426.9 CB Supervision Setting Range (<strong>P922</strong> and <strong>P923</strong>)CB SupervisionSetting rangeMin Max StepCB OPEN SupervisionYes or NoCB OPENING TIME 0.1s 5s 0.05sCB CLOSE SupervisionYes or NoCB CLOSING TIME 0.1s 5s 0.05sNumber operating alarmYes or NoNumber of operations 0 50000 1Close pulse 0.1s 5s 0.05sTrip pulse time 0.1s 5s 0.05s