Technical GuideP92x/EN TD/H42Technical Data<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong> Page 29/427.5 Disturbance record (<strong>P922</strong> and <strong>P923</strong>)The <strong>MiCOM</strong> <strong>P922</strong>-<strong>P923</strong> is able to store up to 5 records:Disturbance RecordsTriggersDataAny selected protection alarm and threshold, logic input,remote commandAC input channelsdigital input and output statesfrequency valueDefault valueSetting rangeMin Max StepRecords number 5 1 5 1Pre-Time 0.1s 0.1 2.9 / 4.9 /6.9 or 8.9Disturb rec Trig ON TRIP ON TRIP or ON INST.TriggerAny selected protection alarm and thresholdLogic inputRemote command7.6 Frequency disturbance record (<strong>P923</strong> only)The <strong>MiCOM</strong> <strong>P923</strong> is able to store one record of 20s.Setting Range Step SizePre – time 5s fixedPost – time 15s fixedSample rate 1 sample/cycle fixedDigital signalsTrigger logic0.1Logic inputs and output contacts status- Instantaneous or time delayed tripping,- Dedicated logic input,- Logic equation,- Remote command.