P92x/EN TD/H42Page 14/42Technical GuideTechnical Data<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong>5.1.4 Definite time delay characteristicsSetting Range Step SizetV< 0 – 599s 0.01stV= Voltage Set 0.5 – 260V 0.1VV>>>= Voltage Set 0.5 – 260V 0.1V−Nominal voltage range: 220 – 480VSetting Range Step SizeV>= Voltage Set 20 – 720V 0.5VV>>= Voltage Set 20 – 960V 0.5VV>>>= Voltage Set 20 – 960V 0.5V5.2.2 Time delay settingsEach voltage element is associated to an independent time delay.Each measuring element time delay can be blocked by the operation of a userdefined logic (optical isolated) input (see “Blocking logic1” or “Blocking logic2”functions).ElementTime delay type1 st stage Definite Time (DT) or IDMT2 nd stage DT3 rd stage DT