P92x/EN TD/H42Page 6/42Technical GuideTechnical Data<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong>1. RATINGS1.1 VoltagesNominal voltageOperating range57 – 130V ph - ph eff 0 to 260V ph - ph eff220 – 480V ph - ph eff 0 to 960V ph - ph effDurationThermal withstand(Vn = 57 – 130V)Continuous 260V ph - ph eff 960V ph - ph effThermal withstand(Vn = 220 – 480V)10 seconds 300V ph - ph eff 1300V ph - ph eff1.2 Auxiliary voltage3 auxiliary voltage ranges are available for the <strong>MiCOM</strong> <strong>P921</strong>-<strong>P922</strong> and <strong>P923</strong> relays,as described below:Phase 2:Nominal auxiliary voltage Vx24-60Vdc;48 -250Vdc/ 48-250 VacOperating rangeDC: ± 20% of VxAC: – 20%, +10% of VxResidual ripple Up to 12%Stored energy time≥50 ms for interruption of VxBurden Stand by: