P92x/EN CM/F22Page 16/26Commissioning Guide<strong>MiCOM</strong> <strong>P921</strong>/<strong>P922</strong>/<strong>P923</strong>5.3.2 <strong>MiCOM</strong> <strong>P921</strong>-<strong>P922</strong>-<strong>P923</strong> relay parametersNote the settings of the <strong>MiCOM</strong> <strong>P921</strong>-<strong>P922</strong>-<strong>P923</strong> relays in the tables below.[59] OVERVOLTAGE Default valuesGroup 1SettingsGroup 2 (<strong>P922</strong>-<strong>P923</strong>)1 st stage activated No No / AND / OR * No / AND / OR *1 st overvoltage stage 130.0V if H1**VV480.0V if H2Time delay type DMT DMT/IDMT * DMT/IDMT *TMS 1.0tRESET V> 0.01s Secs SecstV>= 0.04s Secs Secs2 nd stage activated No No / AND / OR * No / AND / OR *2 nd overvoltage stage 130.0V if H1**VV480.0V if H2tV>>= 0.01s Secs Secs3 rd stage activated No No / AND / OR * No / AND / OR *3 rd overvoltage stage 130.0V if H1**VV480.0V if H2tV>>>= 0.01s Secs SecsHysteresis 0.98[27] UNDERVOLTAGE Default valuesGroup 1SettingsGroup 2 (<strong>P922</strong>-<strong>P923</strong>)1 st stage activated No No / AND / OR * No / AND / OR *1 st undervoltage stage 5.00V if H1**VV20.0V if H2Time delay type DMT DMT/IDMT * DMT/IDMT *TMS 1.0tRESET V< 0.01s Secs SecstV