National Gypsum Construction Guide
National Gypsum Construction Guide The entire - AECinfo.com
National Gypsum Construction Guide The entire - AECinfo.com
- No tags were found...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
GENERAL REFERENCE<br />
<strong>Gypsum</strong> Wallboard Partitions/Solid (CAD FILE NAME GOLDL.DWG OR GOLDL.DXF)<br />
No. Fire Rating Ref. Design No. Description STC Test No.<br />
1 1 hr. FM WP-671 1" (25.4 mm) Fire-Shield Shaftliner with 1/2" (12.7 mm) regular 34 Based on<br />
GA WP 1311 <strong>Gypsum</strong> Wallboard laminated vertically with Sta-Smooth joint NGC 2359<br />
compound, both sides.<br />
QUICK<br />
SELECTOR<br />
2 2 hr. UL U525 1" (25.4 mm) Fire-Shield Shaftliner with 1/2" (12.7 mm) 34 Based on<br />
FM WP-668 Fire-Shield C <strong>Gypsum</strong> Wallboard laminated vertically with NGC 2359<br />
GA WP 1841 Sta-Smooth joint compound, both sides.<br />
3 2 hr. UL U505 1" (25.4 mm) Fire-Shield Shaftliner with 5/8" (15.9 mm)<br />
Fire-Shield Wallboard laminated vertically with<br />
Sta-Smooth joint compound, both sides.<br />
4 2 hr. UL U529 1" (25.4 mm) Fire-Shield Shaftliner with 1/2" (12.7 mm)<br />
Fire-Shield C Wallboard laminated vertically with<br />
Sta-Smooth joint compound, both sides.<br />
QUICK SELECTOR FOR FIRE AND SOUND RATED SYSTEMS<br />
<strong>Gypsum</strong> Wallboard Partitions-Shaftwalls, Area Separation Walls (CAD FILE NAME GOLDM.DWG OR GOLDM.DXF)<br />
No. Fire Rating Ref. Design No. Description STC Test No.<br />
FIRE – SOUND<br />
1 1 hr. UL U499 2 1/2" (63.5 mm), 4" (102 mm) or 6" (152 mm) I-Studs, 37 NGC<br />
FM WP-755 C-T Studs or C-H Studs 24" o.c. (610 mm). 1" (25.4 mm) 2001003<br />
GA WP 6905 Fire-Shield Shaftliner or 1" Fire-Shield Shaftliner XP, one<br />
layer of 5/8" (15.9 mm) Fire-Shield <strong>Gypsum</strong> Wallboard applied<br />
horizontally or vertically on side opposite shaftliner. Fire tested both sides.<br />
1 1/2" (38.1 mm) mineral wool or glass fiber in cavity. 42 NGC 2542<br />
2 2 hr. UL U498 2 1/2" (63.5 mm), 4" (102 mm) or 6" (152 mm) I-Studs, 40 NGC 2618<br />
FM WP-545 C-T Studs or C-H Studs 24" o.c (610 mm). 1" (25.4 mm)<br />
GA WP 7079 Fire-Shield Shaftliner or 1" Fire-Shield Shaftliner XP, and<br />
1 layer of 1/2" (12.7 mm) Fire-Shield C <strong>Gypsum</strong> Wallboard, 1/2"<br />
GA ASW 1215 (12.7 mm) Fire-Shield C Kal-Kore veneer plaster base, or 1/2"<br />
(12.7 mm) Fire-Shield C MR Board applied horizontally on each side.<br />
Horizontal and vertical joints staggered. Fire tested both sides.<br />
.<br />
1 1/2" (38.1 mm) mineral wool or glass fiber in cavity. 45 NGC 2617<br />
U. of Cal. 75-19 5/8" (15.9 mm) Fire-Shield <strong>Gypsum</strong> Wallboard as face layers. 40 Based on<br />
ES 7407 NGC 2618<br />
GA WP 7077<br />
3 2 hr. UL U429 2 1/2" (63.5 mm), 4" (102 mm) or 6" (152 mm) C-T Studs 40 Based on<br />
or C-H Studs 24" o.c. (610 mm), 1" (25.4 mm), 6" NGC 2618<br />
Fire-Shield Shaftliner or 1" Fire-Shield Shaftliner XP and<br />
1 layer of 1/2" (12.7 mm) Fire-Shield C Wallboard applied<br />
vertically on each side. Joints staggered 24" on opposite sides.<br />
1 1/2" (38.1 mm) mineral wool or glass fiber in cavity. 45<br />
Based on<br />
NGC 2617<br />
4 2 hr. UL U497 2 1/2" (63.5 mm), 4" (102 mm) or 6" (152 mm) I-Studs, C-T 40 NGC 2615<br />
FM WP-636 Studs or C-H Studs 24" o.c. (610 mm). 1" (25.4 mm) Fire-Shield<br />
GA WP 7080 Shaftliner or 1" Fire-Shield Shaftliner XP and 2 layers of 1/2" (12.7 mm)<br />
Fire-Shield C <strong>Gypsum</strong> Wallboard, 1/2" (12.7 mm) Fire-Shield C Kal-Kore<br />
veneer plaster base, or 1/2" (12.7 mm) Fire-Shield C MR Board on corridor<br />
side only, base layer horizontal, face layer vertical. Fire tested both sides.<br />
1 1/2" (38.1 mm) mineral wool or glass fiber in cavity. 47 NGC 2616<br />
UL U497 2 1/2" (63.5 mm), 4" (102 mm) or 6" (152 mm) I-Studs, 40 Based on<br />
WHI 651-0500.05 C-T Studs or C-H Studs 24" o.c. (610 mm). 1" (25.4 mm) Fire- NGC 2615-<br />
Shield Shaftliner or 1" Fire-Shield Shaftliner XP and two layers<br />
1/2" (12.7 mm) Fire-Shield C <strong>Gypsum</strong> Wallboard applied<br />
horizontally on corridor side. Fire tested both sides.<br />
U. of Cal. 75-17 2 layers 5/8" (15.9 mm) Fire-Shield Wallboard on corridor side. 40 Based on<br />
ES 7408 NGC 2615<br />
GA WP 7076<br />
NATIONAL GYPSUM QUICK SELECTOR/GENERAL REFERENCE<br />
19