Contents<br />

XRE - Conventional Boilers<br />

XRE3 105 - 330kW<br />

Performance Data<br />

Product<br />

Code<br />

Output<br />

80/60°C kW<br />

Nominal<br />

Input MJ/hr<br />

Burner<br />

Selection<br />

Modulation<br />

Ratio<br />

Waterside<br />

pressure loss<br />

at Δ t = 15<br />

KkPa<br />

Flow Rate<br />

(ΔT 15K) l/s<br />

Combustion<br />

Side Pressure<br />

Drop mbar<br />

Total Water<br />

Volume<br />

litres<br />

Dry Weight<br />

Kg<br />

Power<br />

Supply<br />

V/A/Hz<br />

XRE34 130 560 GS140 up to 1:3 0.5 2.1 0.3 102 620 240/0.75/50<br />

XRE35 169 730 GS200 up to 1:3 0.9 <strong>2.7</strong> 0.6 120 740 240/0.75/50<br />

XRE36 210 910 GS280 up to 1:3 1.5 3.3 1.1 140 850 240/1.04/50<br />

XRE37 249 1080 GS350 up to 1:3 2.1 4.0 1.6 160 985 240/1.54/50<br />

XRE38 291 1260 GS400 up to 1:3 3.0 4.6 2.2 182 1110 240/1.54/50<br />

XRE39 338 1460 GS550 up to 1:3 5.0 5.4 2.5 204 1230 240/2.58/50<br />

CONDENSING &<br />

CONVENTIONAL BOILERS<br />

Dimensional Data<br />

Model A B C Y P ØD<br />

XRE34 995 900 750 292 595 180<br />

XRE35 1165 1070 920 292 765 180<br />

XRE36 1335 1240 1090 292 935 180<br />

XRE37 1505 1410 1260 292 1105 180<br />

XRE38 1675 1580 1430 292 1275 200<br />

XRE39 1845 1750 1600 292 1445 200<br />

All measurements in mm<br />