27.09.2018 Views

AHG Solutions Guide_Edition 2.7

Full Product and Solutions Guide - Automatic Heating Global Pty Ltd

Full Product and Solutions Guide - Automatic Heating Global Pty Ltd

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

Contents<br />

Meridian - Condensing Boilers<br />

Meridian Floor Standing - 120-157kW<br />

• Type A Appliance<br />

• High Efficiency<br />

• Compact Size<br />

• Cascadable<br />

• In Built Header<br />

Meridian<br />

1<br />

Meridian<br />

2<br />

CONDENSING &<br />

CONVENTIONAL BOILERS<br />

• In Built Variable Speed Pump<br />

• Australian Gas Approval<br />

Number: GSCS20215,<br />

VGC40016 (M120LPG)<br />

Overview<br />

Gas Pressure Range<br />

1.1 - <strong>2.7</strong> kPa<br />

Min Water Pressure<br />

100kPa<br />

Max Water Pressure 500kPa<br />

Meridian 150 x 2 with hydraulic separator<br />

Model<br />

Output<br />

50/30ºC<br />

kW<br />

Indoor - Natural Gas<br />

Net<br />

Efficiency<br />

50/30ºC %<br />

Output<br />

80/60°C<br />

kW<br />

Net<br />

Efficiency<br />

80/60°C<br />

%<br />

Nominal<br />

Input<br />

MJ/hr<br />

Modulation<br />

Ratio<br />

Secondary<br />

Side Flow<br />

Rate min/<br />

max L/s*<br />

Water<br />

Pressure<br />

Loss kPa<br />

Total<br />

Water<br />

Volume<br />

litres<br />

Dry<br />

Weight<br />

kg<br />

Dimensions<br />

(mm)<br />

H W D<br />

Air<br />

Flue<br />

Intake<br />

Connection<br />

size<br />

size mm**<br />

mm<br />

Power<br />

Supply<br />

V/A/Hz<br />

M120-IV 120 108.6 107 97.2 450 1:5 0.29/1.43 17 32 200 1207 550 875 Ø100 - 240/2.1/50<br />

M150-IV 157 108.6 144.1 97.3 592 1:5 0.38/1.88 27 32 200 1207 550 875 Ø100 - 240/2.5/50<br />

Indoor - LPG<br />

M120LPG-IV 120 108.6 107 97.2 396 1:5 0.29/1.43 17 32 200 1207 550 875 Ø100 - 240/2.1/50<br />

Outdoor - Natural Gas<br />

M120-OV 120 108.6 107 97.2 450 1:5 0.29/1.43 17 32 200 1243 550 895 Ø100 - 240/2.1/50<br />

M150-OV 157 108.6 144.1 97.3 592 1:5 0.38/1.88 27 32 200 1243 550 895 Ø100 - 240/2.5/50<br />

Outdoor - LPG<br />

M120LPG-OV 120 108.6 107 97.2 396 1:5 0.29/1.43 17 32 200 1243 550 895 Ø100 - 240/2.1/50<br />

All secondary pumps must suck from the top of the hydraulic separator and pump into the field.<br />

** The size of the main flue may vary from the flue connection size subject to various installation criteria.<br />

For assistance with sizing your flue, please discuss your project details with our technical support team.<br />

H<br />

H<br />

D<br />

W<br />

D<br />

W<br />

Indoor<br />

Outdoor<br />

85