AHG Solutions Guide_Edition 2.7
Full Product and Solutions Guide - Automatic Heating Global Pty Ltd
Full Product and Solutions Guide - Automatic Heating Global Pty Ltd
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
HEAT PUMPS<br />
Revere R134A - Water to Water Heat Pumps<br />
Revere R134A<br />
Water to Water<br />
Heat Pump<br />
With the outlet water temperature from<br />
55ºC to 80ºC, as well as space cooling,<br />
Revere R134A Water to Water Heat<br />
Pump is clearly your smartest choice.<br />
Contents<br />
High Efficiency<br />
The unit is capable of producing high temperature outlet<br />
water and simultaneously performs free cooling. The<br />
double effects that it uses the same amount of energy but<br />
provides both hot water and cool air which can lead to<br />
greater cost-savings.<br />
Flexible Installation<br />
The unit can adjust to various installation locations, such as<br />
inside a basement, on the ground floor and even on the roof,<br />
which makes it flexible for fast, low-cost installation.<br />
Combination with Existing Air Cooled Water Chiller<br />
When the unit is working for water heating and space<br />
cooling, the existing air cooled water chillers can be shut off<br />
according to different requirement and condition.<br />
Environmental Friendly<br />
With hi-output, the energy efficiency and environmental<br />
value of the unit can radically surpass that of a single effect<br />
system which can only produce either hot water or cool<br />
air and traditional system that is driven by primary energy<br />
resources, which lessens the impact on the environment.<br />
High ROI<br />
The double effects and high COP offered by the unit is<br />
beneficial in lowering energy bills in the long run.<br />
Application in Various Projects<br />
The unit can be used in commercial and industrial projects,<br />
such as hotels, schools, holiday resorts and factories.<br />
Revere R134A 250S 500S<br />
Testing Condition<br />
Water Source Inlet/Outlet: 20/15ºC<br />
Heating Side Inlet/Outlet: 65/75ºC<br />
Heating Capacity(kW) 64.0 129.0<br />
Cooling Capacity(kW) 40.0 80.0<br />
Power Input(kW) 20.0 40.0<br />
IEER(W/W) 5.2 5.2<br />
Power Supply V/Ph/Hz 380~415/3/50<br />
Compressor Type<br />
Copeland R134a EVI Scroll<br />
Compressor Quantity 2 4<br />
Evaporator Type Tube in Shell Heat Exchanger<br />
Water Flow(m 3 /h) 6.8 13.6<br />
Connection Size(inch) 2.5 2.5<br />
Condenser Type Tube in Shell Heat Exchanger<br />
Water Flow(m 3 /h) 5.6 11.1<br />
Connection Size(inch) 2.5 2.5<br />
Noise dB(A) 56 58<br />
Refrigerant Type<br />
Controller<br />
R134a<br />
<strong>AHG</strong> Controller<br />
Suggest Outlet Water Temp. Range ºC 55 ~ 75<br />
Max. Outlet Water Temp. ºC 80<br />
Casing<br />
Galvanized Metal<br />
Net Dimensions(L/W/H) mm 1172/900/1365 1600/1130/1500<br />
Net Weight kg 455 866<br />
The data above is only a reference, for specific data, please refer to the nameplate on the unit.<br />