04.06.2013 Views

Strata DK 16 Manual

Strata DK 16 Manual

Strata DK 16 Manual

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

INSTALLATION-SITE REQUIREMENTS<br />

SECTION 100-8<strong>16</strong>-202<br />

MARCH 1993<br />

FRONT VIEW<br />

<strong>DK</strong><strong>16</strong> BASE AND EXPANSION<br />

UNIT CLEARANCE<br />

-4 2+----- 20” ------4 2”+- 2”<br />

TOP VIEW<br />

I EXP BASE 3.5” \ WALL<br />

FIGURE 2-3<br />

<strong>DK</strong><strong>16</strong> COMBINED BASE AND<br />

EXPANSION KEY SERVICE UNIT<br />

MINIMUM CLEARANCE REQUIREMENTS<br />

and optioned STRATA <strong>DK</strong><strong>16</strong> system. Refer to<br />

Chapter 4 for <strong>DK</strong><strong>16</strong> key service unit wall mounting<br />

instructions.<br />

3.02 The following conditions must be considered<br />

when selecting a location forthe key service unit(s):<br />

The location MUST BE:<br />

l Dry and clean<br />

l Well ventilated<br />

l Well illuminated<br />

l Easily accessible<br />

t<br />

3.03 If reserve power is to be installed for the<br />

STRATA <strong>DK</strong><strong>16</strong>, the batteries will require a well-<br />

ventilated location close (within nine feet) to the<br />

<strong>DK</strong>SUB<strong>16</strong> (the optional Toshiba-supplied battery<br />

cable is 9 feet in length). The STRATA <strong>DK</strong>8<br />

reserve battery (HPFB) should be mounted di-<br />

rectly above the <strong>DK</strong>SU8 as shown in Figure 2-l.<br />

3.10 Electrical/Environmental Requirements<br />

and Characteristics<br />

3.11 The electrical/environmental requirements<br />

and characteristics for each system are provided<br />

in Table 2-A.<br />

4 GROUNDING REQUIREMENTS<br />

4.00 The systems require a solid earth ground for<br />

proper operation. Failure to provide ground may<br />

lead to confusing trouble symptoms and, in ex-<br />

treme cases, system failure. The AC power cord<br />

contains a conductor for the “third wire ground”<br />

provided by the commercial power outlet. The<br />

third-wire ground should be the only ground nec-<br />

essary for the <strong>DK</strong>8/<strong>DK</strong><strong>16</strong>; this ground must origi-<br />

nate at the buildings main power distribution panel<br />

and have a solid connection to earth ground.<br />

(Figure 2-4)<br />

4.10 Third Wire Ground Test<br />

4.11 Test the “third wire ground” for continuity by<br />

either measuring the resistance between the third<br />

prong terminal (earth ground) and a metal cold<br />

water pipe (maximum: 1 ohm), or by using a<br />

commercially available earth ground indicator. If<br />

neither procedure is possible, perform the follow-<br />

ing earth ground test procedure:<br />

The location MUST NOT BE:<br />

WARNING!<br />

Hazardous voltages that may cause death<br />

l Subject to extreme heat or cold or injury are exposed during the folio wing<br />

l Subject to corrosive fumes, dust, or other air- test. Use great care when working with AC<br />

borne contaminants power line voltage.<br />

l Subject to excessive vibration<br />

l Next to television, radio, office automation, or 1) Obtain a suitable voltmeter, and set it for a<br />

high frequency equipment<br />

possible reading of up to 250 VAC.<br />

2-2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!