15.11.2012 Views

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Error<br />

No.<br />

40*<br />

Master<br />

401<br />

Slave1<br />

402<br />

Slave2<br />

403<br />

Error Type Error Point Main Reasons<br />

Inverter compressor CT<br />

sensor error<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Micom input voltage isn't<br />

within 2.5V ±0.3V at initial<br />

state of power supply<br />

■ Error Diagnosis and Countermeasure Flow Chart<br />

Is input voltage normal?<br />

Yes<br />

Is inverter PCB assembly normal?<br />

Yes<br />

Recheck power and installation condition<br />

* Measuring input voltage<br />

* Inverter PCB assembly<br />

No<br />

No<br />

- 107 -<br />

1. Input voltage abnormal (T-N)<br />

2. ODU inverter PCB damage<br />

(CT sensing part)<br />

Check<br />

R~S/S~T/T~R phase voltage is 380V ±10%<br />

R~N/S~N/T~N phase voltage is 220V ±10%<br />

→ Check connection condition and wiring if power is<br />

abnormal<br />

Replace inverter PCB assembly<br />

* <strong>LG</strong>MV Part<br />

Troubleshooting Guide<br />

<strong>LG</strong>E Internal Use Only

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!