Troubleshooting Guide<br />

05 Indoor & Outdoor unit<br />

transmission error<br />

No signal transmission<br />

between indoor & outdoor<br />

units.<br />

1. Au<strong>to</strong> addressing is not done<br />

2. transmission cable is not connected<br />

3. Short circuit of transmission cable<br />

4. Indoor unit transmission circuit fault<br />

5. Outdoor unit transmission circuit fault<br />

6. Not enough distance between power and transmission<br />

cable?<br />

■ Error diagnosis and countermeasure flow chart<br />

Does all the IDUs show<br />

same error code CH05?<br />

Yes<br />

Is outdoor PCB LED<br />

blinking?<br />

Yes<br />

Check if the<br />

transmission cable is<br />

properly connected<br />

<strong>to</strong> indoor / outdoor<br />

terminal block?*<br />

Yes<br />

No<br />

Check the main power<br />

supply at the ODU<br />

terminal block?<br />

Yes<br />

Is main circuit breaker off?<br />

Yes<br />

* (Note1) Transmission from IDU is normal if voltage<br />

fluctuation(-9V ~ +9V) exists when checking DC voltage<br />

of communication terminal between IDU and ODU<br />

No<br />

No<br />

Is <strong>to</strong>tal number of indoor<br />

units connected displayed<br />

after au<strong>to</strong> addressing?<br />

END<br />

Improper connection of power supply cable<br />

Main power supply problem<br />

Re connect transmission cable<br />

Outdoor PCB fault<br />

Replace after checking<br />

Indoor PCB fault<br />

Replace after checking<br />

No<br />

No<br />

No<br />

Replace the PCB of indoor unit<br />

displayed error<br />

Re-connect after check the<br />

transmission cable of indoor<br />

unit displayed error**<br />

Replace outdoor PCB after<br />

checking<br />

Replace TRANS after checking<br />

Check the insulation of inverter<br />

/ constant compressor and replace<br />

if required<br />

Check the capacity of main circuit<br />

breaker and replace if required<br />

If all ok,<br />

Turn on main circuit breaker<br />

* If the DC voltage between transmission terminal A, B<br />

of indoor unit is fluctuate within (-9V~+9V) then<br />

transmission from outdoor unit is normal<br />

<strong>LG</strong>E Internal Use Only