Checking Method for Key Components<br />

2.5 Inverter IPM Checking Method<br />

CN-P1<br />

CN-N1<br />

N terminal<br />

P terminal<br />

1. Wait until inverter PCB DC voltage is discharged after main power off.<br />

2. Pull out CN-P1, CN-N1 connec<strong>to</strong>rs and U,V,W COMP connec<strong>to</strong>r connected with the inverter PCB.<br />

3. Set multi tester <strong>to</strong> resistance mode.<br />

4. If the value between P and N terminal of IPM is short(0Ω) or open(hundreds MΩ), PCB needs <strong>to</strong> be<br />

replaced.(IPM damaged)<br />

5. In the measured value with resistance mode should be within 28K Ω ±10%.<br />

6. In case measured value is different from the table, PCB needs <strong>to</strong> be replaced.(PCB damaged).<br />

✽ Red(+) and black(-) are the measuring terminals of multi tester.<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

U terminal<br />

P terminal : black (-) N terminal : red (-)<br />

U terminal : red(+) 28K Ω ± 10% Open<br />

V terminal : red(+) 28K Ω ± 10% Open<br />

W terminal : red(+) 28K Ω ± 10% Open<br />

P terminal : red(+) N terminal : red (+)<br />

U terminal : black(-) Open 28K Ω ± 10%<br />

V terminal : black(-) Open 28K Ω ± 10%<br />

W terminal : black(-) Open 28K Ω ± 10%<br />

- 68 -<br />