Function<br />

4.6 Pump Down<br />

This function gathers the refrigerant present in the system <strong>to</strong> ODU<br />

Use this function <strong>to</strong> s<strong>to</strong>re refrigerant of system in ODU for leakage or IDU replacement.<br />

Main PCB<br />

SW02B<br />

Main PCB<br />

SW01V<br />

Close liquid SVC v/v of each unit.<br />

Open gas SVC v/v of each unit.<br />

Power Reset<br />

after Master Unit Dip switch No.10 ON<br />

Note 2)<br />

Low pressure < 229kpa<br />

Main PCB<br />

SW02B<br />

Press the black but<strong>to</strong>n<br />

All IDU cooling operation<br />

Satisfy low<br />

pressure target?<br />

Yes<br />

IDU, ODU OFF<br />

Power reset after Dop switch No.10 off<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Pump down completed<br />

Press the black but<strong>to</strong>n<br />

- 40 -<br />

Note 1)<br />

ODU SVC V/V Setting<br />

Close Open<br />

Ball Valve(Liquid Pipe)<br />

Elbow<br />

Ball Valve(Gas Pipe)<br />

ODU SVC V/V Setting<br />

Close Close<br />

Ball Valve(Liquid Pipe)<br />

[Note]<br />

If is displayed, close gas SVC V/V of all ODU immediately.<br />

If low pressure descends below 229 kPa, the system turns off au<strong>to</strong>matically. Close the gas SVC V/V immediately.<br />

Caution<br />

1.Use pump down function within guaranteed temperature range<br />

IDU : 20~32°C<br />

ODU : 5~40°C<br />

2. Make certain that IDU doesn't run with thermo off mode during operation<br />

3. Maximum operation time of pump down function is 30 min.<br />

(in case low pressure doesn't go down)<br />

4. Press black+red but<strong>to</strong>n during operation <strong>to</strong> end pump down.(IDU,ODU off)<br />

No<br />

Elbow<br />

Ball Valve(Gas Pipe)<br />

<strong>LG</strong>E Internal Use Only