15.11.2012 Views

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Error<br />

No.<br />

42*<br />

Master 421<br />

Slave1 422<br />

Slave2 423<br />

43*<br />

Master 431<br />

Slave1 432<br />

Slave2 433<br />

Error Type Error Point Main Reasons<br />

Sensor error of low<br />

pressure<br />

Sensor error of high<br />

pressure<br />

■ Error diagnosis and countermeasure flow chart<br />

Is sensor connected<br />

<strong>to</strong> PCB correctly?<br />

Yes<br />

After replacement of<br />

outdoor unit main PCB<br />

is the system normal?<br />

Yes<br />

END<br />

No<br />

No<br />

Low pressure sensor<br />

Abnormal value of<br />

sensor<br />

(Open/Short)<br />

Abnormal value of<br />

sensor<br />

(Open/Short)<br />

High pressure sensor<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Connect sensor <strong>to</strong> PCB correctly<br />

Replace corresponding<br />

pressure sensor<br />

- 109 -<br />

Troubleshooting Guide<br />

1. Bad connection of low pressure connec<strong>to</strong>r<br />

2. Defect of low pressure connec<strong>to</strong>r (Open/Short)<br />

3. Defect of outdoor PCB<br />

1. Bad connection of high pressure connec<strong>to</strong>r<br />

2. Defect of high pressure connec<strong>to</strong>r (Open/Short)<br />

3. Defect of outdoor PCB<br />

<strong>LG</strong>E Internal Use Only