1.3 Master and slave Unit's EEV control<br />

(1) Main EEV control<br />

Main EEV operates with fuzzy control rules <strong>to</strong> keep the degree of super Heat(Superheat) (about 3°C)at<br />

the evapora<strong>to</strong>r outlet stable during heating mode<br />

The degree of Superheat = Tsuction - Tevaporation<br />

Tsuction : temperature at suction pipe sensor(°C)<br />

Tevaporation : evaporation temperature equivalent <strong>to</strong> low pressure(°C)<br />

(2) Subcooling EEV control(about 15°C)<br />

Subcooling EEV works with fuzzy rules <strong>to</strong> keep the degree of Subcool at the outlet of subcooler during<br />

cooling mode<br />

The degree of Subcool = Tcondensation - Tliquid<br />

Tliquid : temperature at outlet of subcooler(°C)<br />

Tcondensation : condensation temperature equivalent <strong>to</strong> high pressure(°C)<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 23 -<br />

Function<br />

(3) Avoiding excessive high discharge temperature : when main EEV opens some given opening (R22 :<br />

1000pls, R410A : 800 pls) and discharge temperature is above 85°C in heating operation, subcooling<br />

EEV may control the "subcooling out temperature-evaporating temperature" <strong>to</strong> be some given difference.<br />