Function<br />

3.4 Liquid back control<br />

■ Cooling mode<br />

Discharge temperature Indoor unit’s EEV<br />

Tdis < Tc + 12˚C<br />

Tdis > Tc + 16˚C<br />

■ Heating mode<br />

❇ The logic starts after 9 min. on heating mode and 4 min. on cooling mode from the compressor running.<br />

3.5 Phase detection<br />

■ Main unit<br />

If a phase is missed, 7-segment displays 50* on main PCB.<br />

If phases are reversed, 7-segment displays 54* on main PCB.<br />

3.6 Pressure switch<br />

- Main has pressure sensing switch in series between compressor and power relay.<br />

- The state of pressure sensing switch is normally on. It has small electric current from 220V AC. Never <strong>to</strong>uch<br />

the connecting terminal with hand nor short two wires directly.<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

SH increasing control<br />

Normal SH control<br />

Discharge temperature Outdoor unit ’s EEV<br />

Tdis < Tc + 17˚C<br />

Tdis > Tc + 18˚C<br />

SH increasing control<br />

Normal SH control<br />

- 30 -<br />