15.11.2012 Views

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

to download LG Multi V Plus - Hawco

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Error<br />

No.<br />

60*<br />

Master<br />

601<br />

Slave1<br />

602<br />

Slave2<br />

603<br />

Error Type Error Point Main Reasons<br />

Inverter PCB EEPROM<br />

error<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

EEPROM Access error and<br />

Check SUM error<br />

■ Error Diagnosis and Countermeasure Flow Chart<br />

Is EEPROM insertion normal?<br />

Yes<br />

Is inverter PCB assembly normal?<br />

Yes<br />

Recheck power and installation condition<br />

* Inverter EEPROM inserting point<br />

No<br />

No<br />

* Right inserting direction of inverter EEPROM<br />

❊ Note : Replace after power off<br />

- 117 -<br />

Troubleshooting Guide<br />

1. EEPROM contact defect/wrong insertion<br />

2. Different EEPROM Version<br />

3. ODU inverter PCB assembly damage<br />

1.Check EEPROM insert direction/connection condition<br />

2.Check EEPROM Check SUM<br />

→ Replace if abnormality found<br />

Replace inverter PCB assembly<br />

EEPROM enlarged picture<br />

<strong>LG</strong>E Internal Use Only