to download LG Multi V Plus - Hawco
to download LG Multi V Plus - Hawco
to download LG Multi V Plus - Hawco
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Error<br />
No.<br />
60*<br />
Master<br />
601<br />
Slave1<br />
602<br />
Slave2<br />
603<br />
Error Type Error Point Main Reasons<br />
Inverter PCB EEPROM<br />
error<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
EEPROM Access error and<br />
Check SUM error<br />
■ Error Diagnosis and Countermeasure Flow Chart<br />
Is EEPROM insertion normal?<br />
Yes<br />
Is inverter PCB assembly normal?<br />
Yes<br />
Recheck power and installation condition<br />
* Inverter EEPROM inserting point<br />
No<br />
No<br />
* Right inserting direction of inverter EEPROM<br />
❊ Note : Replace after power off<br />
- 117 -<br />
Troubleshooting Guide<br />
1. EEPROM contact defect/wrong insertion<br />
2. Different EEPROM Version<br />
3. ODU inverter PCB assembly damage<br />
1.Check EEPROM insert direction/connection condition<br />
2.Check EEPROM Check SUM<br />
→ Replace if abnormality found<br />
Replace inverter PCB assembly<br />
EEPROM enlarged picture<br />
<strong>LG</strong>E Internal Use Only