Outdoor unit related error<br />

Display Title Cause of Error<br />

1 1 4<br />

1 1 5<br />

1 5 1<br />

1 7 3<br />

1 9 3<br />

1<br />

2<br />

3<br />

4<br />

1<br />

2<br />

3<br />

4<br />

1<br />

2<br />

3<br />

4<br />

1<br />

2<br />

3<br />

4<br />

1<br />

2<br />

3<br />

4<br />

Master Outdoor Unit Subcooling<br />

Inlet Temperature Sensor Error<br />

Slave1 Outdoor Unit Subcooling<br />

Inlet Temperature Sensor Error<br />

Slave2 Outdoor Unit Subcooling<br />

Inlet Temperature Sensor Error<br />

Slave3 Outdoor Unit Subcooling<br />

Inlet Temperature Sensor Error<br />

Master Outdoor Unit Subcooling<br />

Outlet Temperature Sensor Error<br />

Slave1 Outdoor Unit Subcooling<br />

Outlet Temperature Sensor Error<br />

Slave2 Outdoor Unit Subcooling<br />

Outlet Temperature Sensor Error<br />

Slave3 Outdoor Unit Subcooling<br />

Outlet Temperature Sensor Error<br />

Failure of operation mode conversion<br />

at Master Outdoor Unit<br />

Failure of operation mode conversion<br />

at Slave1 Outdoor Unit<br />

Failure of operation mode conversion<br />

at Slave2 Outdoor Unit<br />

Failure of operation mode conversion<br />

at Slave3 Outdoor Unit<br />

Master Outdoor Unit Constant<br />

Speed Compressor Fault<br />

Slave1 Outdoor Unit Constant<br />

Speed Compressor Fault<br />

Slave2 Outdoor Unit Constant<br />

Speed Compressor Fault<br />

Slave3 Outdoor Unit Constant<br />

Speed Compressor Fault<br />

Excessive increase of Master<br />

Outdoor Unit Fan PCB Heat Sink<br />

Temperature<br />

Excessive increase of Slave1<br />

Outdoor Unit Fan PCB Heat Sink<br />

Temperature<br />

Excessive increase of Slave2<br />

Outdoor Unit Fan PCB Heat Sink<br />

Temperature<br />

Excessive increase of Slave3<br />

Outdoor Unit Fan PCB Heat Sink<br />

Temperature<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

- 81 -<br />

Self-diagnosis function<br />

Master Outdoor Unit Subcooling Inlet Temperature<br />

Sensor open or short<br />

Slave1 Outdoor Unit Subcooling Inlet Temperature<br />

Sensor open or short<br />

Slave2 Outdoor Unit Subcooling Inlet Temperature<br />

Sensor open or short<br />

Slave3 Outdoor Unit Subcooling Inlet Temperature<br />

Sensor open or short<br />

Master Outdoor Unit Subcooling Outlet Temperature<br />

Sensor open or short<br />

Slave1 Outdoor Unit Subcooling Outlet Temperature<br />

Sensor open or short<br />

Slave2 Outdoor Unit Subcooling Outlet Temperature<br />

Sensor open or short<br />

Slave3 Outdoor Unit Subcooling Outlet Temperature<br />

Sensor open or short<br />

Pressure unbalance between outdoor units<br />

Pressure unbalance between outdoor units<br />

Pressure unbalance between outdoor units<br />

Pressure unbalance between outdoor units<br />

Comp locking, Check Valve leakage, comp dielectric<br />

break down at Master Outdoor Unit<br />

Comp locking, Check Valve leakage, comp dielectric at<br />

Slave1 Outdoor Unit<br />

Comp locking, Check Valve leakage, comp dielectric at<br />

Slave2 Outdoor Unit<br />

Comp locking, Check Valve leakage, comp dielectric at<br />

Slave3 Outdoor Unit<br />

Master Outdoor Unit Fan Inverter PCB Temperature is<br />

Over 95°C<br />

Slave1 Outdoor Unit Fan Inverter PCB Temperature is<br />

Over 95°C<br />

Slave2 Outdoor Unit Fan Inverter PCB Temperature is<br />

Over 95°C<br />

Slave3 Outdoor Unit Fan Inverter PCB Temperature is<br />

Over 95°C<br />