1. Checks Before Test Run<br />
Check <strong>to</strong> see whether there is any refrigerant leakage, and slack of power or transmission cable.<br />
Confirm that 500 V megger shows 2.0 MΩ or more between power supply terminal block and ground.<br />
Do not operate in the case of 2.0 MΩ or less.<br />
NOTE: Never carry out megaohm check over terminal control board. Otherwise the control board<br />
would be broken.<br />
Immediately after mounting the unit or after leaving it turned off for an extended length of time,<br />
the resistance of the insulation between the power supply terminal board and the ground may<br />
decrease <strong>to</strong> approx. 2 MΩ as a result of refrigerant accumulating in the internal compressor.<br />
If the insulation resistance is less than 2 MΩ, turning on the main power supply and energizing<br />
the crankcase heater for more than 6 hours will cause the refrigerant <strong>to</strong> evaporate, increasing<br />
the insulation resistance.<br />
Check if high/low pressure common pipe, liquid pipe and gas pipe valves are fully opened.<br />
NOTE: Be sure <strong>to</strong> tighten caps.<br />
Check if there are any problems in au<strong>to</strong>matic addressing or not:<br />
Check and confirm that there are no error messages in the display of indoor units or remote controls<br />
and LED in outdoor units.<br />
CAUTION<br />
when cutting main power of the <strong>Multi</strong> V<br />
• Always apply main power of the outdoor unit during use of product<br />
(cooling season/heating season).<br />
• Always apply power before 6 hours <strong>to</strong> heat the crank case heater where performing test run after<br />
installation of product. It may result in burning out of the compressor if not preheating the crank<br />
case with the electrical heater for more than 6 hours.(In case of the outdoor temperature below 10°C)<br />
• When operating the unit after powering off, au<strong>to</strong>matically run in<strong>to</strong> in the preheat mode for 3 hours<br />
and "PH" is indicated on the outdoor unit 7-Segment.<br />
CAUTION<br />
Preheat of compressor<br />
• Start preheat operation for 3 hours after supplying main power.<br />
• In case that the outdoor temperature is low, be sure <strong>to</strong> supply power 6 hours before operation so<br />
that the heater is heated(insufficient heating may cause damage of the compressor.)<br />