Troubleshooting Guide<br />

Error<br />

No.<br />

10<br />

Error Type Error Point Main Reasons<br />

Indoor unit BLDC fan mo<strong>to</strong>r<br />

failure<br />

Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />

Only for training and service purposes<br />

Indoor BLDC fan mo<strong>to</strong>r<br />

feedback signal is absent<br />

(for 50 sec.)<br />

■ Error diagnosis and countermeasure flow chart<br />

Is connec<strong>to</strong>r<br />

connection proper?<br />

Yes<br />

Is fan mo<strong>to</strong>r<br />

normal?*<br />

Yes<br />

Replace indoor unit PCB **<br />

No<br />

No<br />

Connect properly<br />

Replace indoor unit fan mo<strong>to</strong>r<br />

* It is normal when check hall sensor of indoor fan mo<strong>to</strong>r as shown below<br />

1 4 5 6 7<br />

<br />

Each termainl with the tester<br />

Tester Normal resistance(±10%)<br />

+ - TH chassis TD chassis<br />

1 4 ∞ ∞<br />

5<br />

6<br />

7<br />

4<br />

4<br />

4<br />

hundreds kΩ hundreds kkΩ<br />

∞ ∞<br />

hundreds kΩ hundreds kΩ<br />

** Replace the indoor unit PCB, and then make sure <strong>to</strong> do Au<strong>to</strong> addressing and input the<br />

address of central control<br />

(Notice: The connection of mo<strong>to</strong>r connec<strong>to</strong>r <strong>to</strong> PCB should be done under no power<br />

supplying <strong>to</strong> PCB)<br />

- 90 -<br />

1. Mo<strong>to</strong>r connec<strong>to</strong>r connection fault<br />

2. Indoor PCB fault<br />

3. Mo<strong>to</strong>r fault<br />

<strong>LG</strong>E Internal Use Only