Function<br />
■ Example. Slave2 ODU Inv Comp failure<br />
Heating mode<br />
Slave2<br />
Comp failure unit<br />
gas<br />
pipe<br />
liquid<br />
pipe<br />
1. Close liquid pipe and common pipe of the unit for pump out operation.<br />
2. Operate pump out<br />
3. Close gas pipe of unit after completion<br />
4. End pump out<br />
5. Close common pipe of no.1,2.<br />
6. Eliminate refrigerant in common pipe after opening the common pipe of corresponding ODU.<br />
Replace compressor and perform vacuum.<br />
7. Add the refrigerant with au<strong>to</strong> charging function<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
Heating mode<br />
Slave1<br />
gas<br />
pipe<br />
- 42 -<br />