Function<br />
3. Protection control<br />
3.1 Pressure protection control<br />
3.1.1 Pressure control on cooling mode<br />
■ High pressure control<br />
■ Low pressure control<br />
3.1.2 Pressure control on heating mode<br />
■ High pressure control<br />
Pressure Range Compressor Fan Hot_gas<br />
Pd ≥ 4003kPa S<strong>to</strong>p S<strong>to</strong>p On<br />
Pd > 3676kPa -5Hz/4sec. 1) -50RPM/4sec.<br />
Pd ≤ 3448kPa Normal control Normal control<br />
Pd ≤ Target press Normal control off<br />
■ Low pressure control<br />
2<br />
2<br />
Pressure Range Compressor Fan Hot_gas<br />
Pd ≥ 4003 kPa S<strong>to</strong>p S<strong>to</strong>p<br />
Pd > 3676 kPa -5Hz/4sec. +100RPM/4sec.<br />
Pd ≥ 3448 kPa Frequency holding Normal control<br />
Pd < 3284 kPa Normal control -<br />
Pressure Range Compressor Fan Hot_gas<br />
Ps ≤ 229 kPa<br />
1 after 1min<br />
Ps ≤ 229 kPa before<br />
1min<br />
❈ Frequency holding : frequency (or RPM) is not increasing ( can decrease )<br />
Pressure Range Compressor Fan Hot_gas<br />
1 Ps ≤ 229 kPa<br />
after 1min<br />
Ps ≤ 229 kPa before<br />
1min<br />
❈ Frequency holding : frequency (or RPM) is not increasing ( can decrease )<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
S<strong>to</strong>p S<strong>to</strong>p<br />
-5Hz/4sec. -100RPM/4sec.<br />
Ps ≤ 242 kPa Normal control Normal control<br />
3<br />
Ps ≥ 399 kPa Normal control Off<br />
S<strong>to</strong>p S<strong>to</strong>p<br />
-5Hz/4sec. +100RPM/4sec.<br />
3 Ps ≤ 242 kPa Frequency holding Normal control<br />
Ps ≤ 268kPa<br />
Normal control<br />
Ps > 307kPa Off<br />
- 28 -<br />