Function<br />
4.5 Refrigerant Checking Function<br />
1. This function charges appropriate amount of refrigerant au<strong>to</strong>matically through cycle operation.<br />
2. This function judges refrigerant leakage and overcharging.<br />
3. It can be used with refrigerant au<strong>to</strong> charging function.<br />
Main<br />
PCB<br />
SW01S<br />
Main<br />
PCB<br />
SW01B<br />
SW02B<br />
Main<br />
PCB<br />
SW01V<br />
Main<br />
PCB<br />
SW01V<br />
Start<br />
Wait for 3 min. after power reset<br />
Set the Dip S/W.<br />
Refrigerant Checking : 1,2,7,14 ON<br />
Press the black but<strong>to</strong>n on main PCB.<br />
( Press until ‘608’ is displayed )<br />
Press the black but<strong>to</strong>n on main PCB<br />
IDU runs with cooling mode in order.<br />
Excess of<br />
Refrigerant<br />
Main<br />
PCB<br />
SW01V<br />
Judging<br />
Refrigerant<br />
Amount<br />
Scarcity of<br />
Refrigerant<br />
IDU, ODU are turned off<br />
Press the black but<strong>to</strong>n on main PCB<br />
Press the black but<strong>to</strong>n for 2 sec. after<br />
turning off all of dip S/W.<br />
Completed<br />
Copyright ©2007 <strong>LG</strong> Electronics. Inc. All right reserved.<br />
Only for training and service purposes<br />
Impossible<br />
To Judge<br />
Note<br />
1. In case air temperature is out of guaranteed<br />
temperature, refrigerant checking function may end<br />
without performing refrigerant checking. Use<br />
guaranteed temperature range only.<br />
2. During the process of judging refrigerant amount, if<br />
the cycle isn't stable, refrigerant checking function<br />
may end without performing refrigerant checking.<br />
- 38 -<br />